Add optional cable-sizing module
Per-circuit cross-section recommendation as a separate module attached to the circuit list. It never writes project data itself: "Übernehmen" applies cable type, cross-section and length through the regular circuit.update command, so revisions and Undo/Redo stay intact. - Pure domain module (src/cable-sizing) with IEC 60364-5-52:2009 Annex B tables for PVC and XLPE, copper and aluminium, methods A1, A2, B1, B2, C, D1, D2 and E. Every value was cross-checked against public reproductions; where sources differ the lower value is used (docs/cable-sizing-module.md). - Temperature and grouping between table values round to the safer value; values outside the tables return no result instead of a factor of 1. Ground methods use B.52.18 (D2) and B.52.19 A (D1). - Overload protection: circuit-breakers In <= Iz; gG fuses additionally I2 <= 1.45 Iz with I2 = 1.6/1.9/2.1 In. - Inputs prefilled from the circuit: power, phase (group or device rows), project voltage, power-weighted cos phi, length and protective device. - Opened from a "Leitungsberechnung" button in the row actions, not from a grid cell, so cable cells keep the spreadsheet behavior. - Stateless API under /api/cable-sizing; no database table or migration. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
This commit is contained in:
parent
d95f0bf5c0
commit
49488f4e1b
17 changed files with 1999 additions and 4 deletions
|
|
@ -391,6 +391,28 @@ inverse command. The former direct restore/reconnect endpoints are removed.
|
|||
`displayName` is included in the comparison but is not selected by default in the UI. Updating a
|
||||
project device never triggers synchronization implicitly.
|
||||
|
||||
## Cable Sizing (optional module)
|
||||
|
||||
Stateless calculator endpoints mounted at `/api/cable-sizing`. They neither
|
||||
read nor write project data; applying a result uses `circuit.update` through
|
||||
`POST /projects/:projectId/commands`.
|
||||
|
||||
- `POST /cable-sizing/calculate`
|
||||
- request: phase, mode (`power` | `current`), powerKw or currentA, cosPhi,
|
||||
voltage, lengthM, layingMethod (`A1` | `A2` | `B1` | `B2` | `C` | `D1` |
|
||||
`D2` | `E`), conductorMaterial, insulation (`pvc` | `xlpe`),
|
||||
ambientTemperatureC, groupingCircuits, maxVoltageDropPercent,
|
||||
harmonicNeutralLoad, optional `existingProtection`
|
||||
(`{ ratedCurrentA, kind: "breaker" | "fuse" }`) and circuitCategory
|
||||
- returns `{ "result": { ... }, "alerts": [ ... ] }`; `result.supported`
|
||||
is `false` with `unsupportedReason` when temperature or grouping lie
|
||||
outside the tables
|
||||
- unknown fields are rejected (`400`)
|
||||
- `GET /cable-sizing/laying-methods`
|
||||
- `GET /cable-sizing/insulation-materials`
|
||||
|
||||
Full request example and calculation rules: `docs/cable-sizing-module.md`.
|
||||
|
||||