forked from jappel/leistungsbilanz-ts
Add optional cable-sizing module
Per-circuit cross-section recommendation as a separate module attached to the circuit list. It never writes project data itself: "Übernehmen" applies cable type, cross-section and length through the regular circuit.update command, so revisions and Undo/Redo stay intact. - Pure domain module (src/cable-sizing) with IEC 60364-5-52:2009 Annex B tables for PVC and XLPE, copper and aluminium, methods A1, A2, B1, B2, C, D1, D2 and E. Every value was cross-checked against public reproductions; where sources differ the lower value is used (docs/cable-sizing-module.md). - Temperature and grouping between table values round to the safer value; values outside the tables return no result instead of a factor of 1. Ground methods use B.52.18 (D2) and B.52.19 A (D1). - Overload protection: circuit-breakers In <= Iz; gG fuses additionally I2 <= 1.45 Iz with I2 = 1.6/1.9/2.1 In. - Inputs prefilled from the circuit: power, phase (group or device rows), project voltage, power-weighted cos phi, length and protective device. - Opened from a "Leitungsberechnung" button in the row actions, not from a grid cell, so cable cells keep the spreadsheet behavior. - Stateless API under /api/cable-sizing; no database table or migration. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
This commit is contained in:
parent
d95f0bf5c0
commit
49488f4e1b
17 changed files with 1999 additions and 4 deletions
689
src/cable-sizing/domain/cable-sizing-calculation.ts
Normal file
689
src/cable-sizing/domain/cable-sizing-calculation.ts
Normal file
|
|
@ -0,0 +1,689 @@
|
|||
// Pure cable sizing domain logic. No imports from db/, server/ or frontend/;
|
||||
// the module is an optional calculator attached to the circuit list and never
|
||||
// writes project data itself (see docs/cable-sizing-module.md).
|
||||
//
|
||||
// Reference data: IEC 60364-5-52:2009, Annex B (tables B.52.2 to B.52.5,
|
||||
// B.52.10 to B.52.19). Every value was cross-checked against publicly
|
||||
// available reproductions of these tables; where sources disagreed the lower,
|
||||
// i.e. safer, value is used. The table-by-table verification record is in
|
||||
// docs/cable-sizing-module.md. National tables (DIN VDE 0298-4) may differ in
|
||||
// individual values and must be checked by the planner against the norm text.
|
||||
|
||||
// -- Reference installation methods (IEC 60364-5-52, Table B.52.1) ----------
|
||||
|
||||
export const LAYING_METHODS = ["A1", "A2", "B1", "B2", "C", "D1", "D2", "E"] as const;
|
||||
export type LayingMethod = (typeof LAYING_METHODS)[number];
|
||||
|
||||
export const LAYING_METHOD_GROUP: Record<LayingMethod, "air" | "ground"> = {
|
||||
A1: "air",
|
||||
A2: "air",
|
||||
B1: "air",
|
||||
B2: "air",
|
||||
C: "air",
|
||||
E: "air",
|
||||
D1: "ground",
|
||||
D2: "ground",
|
||||
};
|
||||
|
||||
export const LAYING_METHOD_LABELS: Record<LayingMethod, string> = {
|
||||
A1: "A1 – Einzeladern im Rohr in wärmegedämmter Wand",
|
||||
A2: "A2 – Mehradrige Leitung im Rohr in wärmegedämmter Wand",
|
||||
B1: "B1 – Einzeladern im Rohr auf oder in der Wand",
|
||||
B2: "B2 – Mehradrige Leitung im Rohr auf oder in der Wand",
|
||||
C: "C – Mehradrige Leitung direkt auf oder in der Wand",
|
||||
D1: "D1 – Leitung im Rohr oder Kabelschutzrohr im Erdreich",
|
||||
D2: "D2 – Kabel direkt im Erdreich",
|
||||
E: "E – Mehradrige Leitung frei in Luft",
|
||||
};
|
||||
|
||||
// -- Insulation / conductor material ----------------------------------------
|
||||
|
||||
export const INSULATION_MATERIALS = ["pvc", "xlpe"] as const;
|
||||
export type InsulationMaterial = (typeof INSULATION_MATERIALS)[number];
|
||||
|
||||
export const INSULATION_MATERIAL_LABELS: Record<InsulationMaterial, string> = {
|
||||
pvc: "PVC (70 °C), z. B. NYM, NYY",
|
||||
xlpe: "VPE/XLPE (90 °C), z. B. N2XH, NHXH",
|
||||
};
|
||||
|
||||
export const CONDUCTOR_MATERIALS = ["copper", "aluminum"] as const;
|
||||
export type ConductorMaterial = (typeof CONDUCTOR_MATERIALS)[number];
|
||||
|
||||
// -- Harmonic neutral loading (IEC 60364-5-52, Annex E, three-phase only) ---
|
||||
|
||||
export const HARMONIC_NEUTRAL_LOAD_OPTIONS = [
|
||||
"none",
|
||||
"15to33Percent",
|
||||
"over33Percent",
|
||||
] as const;
|
||||
export type HarmonicNeutralLoad = (typeof HARMONIC_NEUTRAL_LOAD_OPTIONS)[number];
|
||||
|
||||
export const HARMONIC_NEUTRAL_LOAD_LABELS: Record<HarmonicNeutralLoad, string> = {
|
||||
none: "Keine nennenswerte 3. Harmonische (< 15 %) – Standardfall",
|
||||
"15to33Percent": "3. Harmonische 15–33 % – Reduktionsfaktor 0,86",
|
||||
over33Percent: "3. Harmonische > 33 % – Neutralleiter wie Außenleiter dimensionieren",
|
||||
};
|
||||
|
||||
export const HARMONIC_REDUCTION_FACTOR = 0.86;
|
||||
|
||||
// -- Current-carrying capacity tables ----------------------------------------
|
||||
|
||||
export const CROSS_SECTIONS_MM2 = [
|
||||
1.5, 2.5, 4, 6, 10, 16, 25, 35, 50, 70, 95, 120, 150, 185, 240,
|
||||
] as const;
|
||||
|
||||
type CoreCount = 2 | 3;
|
||||
type CapacityRow = readonly (number | null)[];
|
||||
type CapacityTable = Record<LayingMethod, Record<CoreCount, CapacityRow>>;
|
||||
|
||||
const n = null;
|
||||
|
||||
/** Iz in A at 30 °C air / 20 °C ground, soil resistivity 2.5 K·m/W. */
|
||||
export const CURRENT_CAPACITY_A: Record<
|
||||
InsulationMaterial,
|
||||
Record<ConductorMaterial, CapacityTable>
|
||||
> = {
|
||||
pvc: {
|
||||
copper: {
|
||||
// B.52.2 / B.52.4; E: B.52.10 multi-core. A1 2L 240 mm²: sources 320/321 → 320.
|
||||
// E 3L 70/120 mm²: sources 196/198 and 276/278 → 196 and 276.
|
||||
A1: {
|
||||
2: [14.5, 19.5, 26, 34, 46, 61, 80, 99, 119, 151, 182, 210, 240, 273, 320],
|
||||
3: [13.5, 18, 24, 31, 42, 56, 73, 89, 108, 136, 164, 188, 216, 245, 286],
|
||||
},
|
||||
A2: {
|
||||
2: [14, 18.5, 25, 32, 43, 57, 75, 92, 110, 139, 167, 192, 219, 248, 291],
|
||||
3: [13, 17.5, 23, 29, 39, 52, 68, 83, 99, 125, 150, 172, 196, 223, 261],
|
||||
},
|
||||
B1: {
|
||||
2: [17.5, 24, 32, 41, 57, 76, 101, 125, 151, 192, 232, 269, 300, 341, 400],
|
||||
3: [15.5, 21, 28, 36, 50, 68, 89, 110, 134, 171, 207, 239, 262, 296, 346],
|
||||
},
|
||||
B2: {
|
||||
2: [16.5, 23, 30, 38, 52, 69, 90, 111, 133, 168, 201, 232, 258, 294, 344],
|
||||
3: [15, 20, 27, 34, 46, 62, 80, 99, 118, 149, 179, 206, 225, 255, 297],
|
||||
},
|
||||
C: {
|
||||
2: [19.5, 27, 36, 46, 63, 85, 112, 138, 168, 213, 258, 299, 344, 392, 461],
|
||||
3: [17.5, 24, 32, 41, 57, 76, 96, 119, 144, 184, 223, 259, 299, 341, 403],
|
||||
},
|
||||
D1: {
|
||||
2: [22, 29, 37, 46, 60, 78, 99, 119, 140, 173, 204, 231, 261, 292, 336],
|
||||
3: [18, 24, 30, 38, 50, 64, 82, 98, 116, 143, 169, 192, 217, 243, 280],
|
||||
},
|
||||
D2: {
|
||||
2: [22, 28, 38, 48, 64, 83, 110, 132, 156, 192, 230, 261, 293, 331, 382],
|
||||
3: [19, 24, 33, 41, 54, 70, 92, 110, 130, 162, 193, 220, 246, 278, 320],
|
||||
},
|
||||
E: {
|
||||
2: [22, 30, 40, 51, 70, 94, 119, 148, 180, 232, 282, 328, 379, 434, 514],
|
||||
3: [18.5, 25, 34, 43, 60, 80, 101, 126, 153, 196, 238, 276, 319, 364, 430],
|
||||
},
|
||||
},
|
||||
aluminum: {
|
||||
// B.52.2 / B.52.4 aluminium; E: B.52.11. No values below 2.5 mm²
|
||||
// (D2 below 16 mm²).
|
||||
A1: {
|
||||
2: [n, 15, 20, 26, 36, 48, 63, 77, 93, 118, 142, 164, 189, 215, 252],
|
||||
3: [n, 14, 18.5, 24, 32, 43, 57, 70, 84, 107, 129, 149, 170, 194, 227],
|
||||
},
|
||||
A2: {
|
||||
2: [n, 14.5, 19.5, 25, 33, 44, 58, 71, 86, 108, 130, 150, 172, 195, 229],
|
||||
3: [n, 13.5, 17.5, 23, 31, 41, 53, 65, 78, 98, 118, 135, 155, 176, 207],
|
||||
},
|
||||
B1: {
|
||||
2: [n, 18.5, 25, 32, 44, 60, 79, 97, 118, 150, 181, 210, 234, 266, 312],
|
||||
3: [n, 16.5, 22, 28, 39, 53, 70, 86, 104, 133, 161, 186, 204, 230, 269],
|
||||
},
|
||||
B2: {
|
||||
2: [n, 17.5, 24, 30, 41, 54, 71, 86, 104, 131, 157, 181, 201, 230, 269],
|
||||
3: [n, 15.5, 21, 27, 36, 48, 62, 77, 92, 116, 139, 160, 176, 199, 232],
|
||||
},
|
||||
C: {
|
||||
2: [n, 21, 28, 36, 49, 66, 83, 103, 125, 160, 195, 226, 261, 298, 352],
|
||||
3: [n, 18.5, 25, 32, 44, 59, 73, 90, 110, 140, 170, 197, 227, 259, 305],
|
||||
},
|
||||
D1: {
|
||||
2: [n, 22, 29, 36, 47, 61, 77, 93, 109, 135, 159, 180, 204, 228, 262],
|
||||
3: [n, 18.5, 24, 30, 39, 50, 64, 77, 91, 112, 132, 150, 169, 190, 218],
|
||||
},
|
||||
D2: {
|
||||
2: [n, n, n, n, n, 63, 82, 98, 117, 145, 173, 200, 224, 255, 298],
|
||||
3: [n, n, n, n, n, 53, 69, 83, 99, 122, 148, 169, 189, 214, 250],
|
||||
},
|
||||
E: {
|
||||
2: [n, 23, 31, 39, 54, 73, 89, 111, 135, 173, 210, 244, 282, 322, 380],
|
||||
3: [n, 19.5, 26, 33, 46, 61, 78, 96, 117, 150, 183, 212, 245, 280, 330],
|
||||
},
|
||||
},
|
||||
},
|
||||
xlpe: {
|
||||
copper: {
|
||||
// B.52.3 / B.52.5; E: B.52.12 multi-core.
|
||||
A1: {
|
||||
2: [19, 26, 35, 45, 61, 81, 106, 131, 158, 200, 241, 278, 318, 362, 424],
|
||||
3: [17, 23, 31, 40, 54, 73, 95, 117, 141, 179, 216, 249, 285, 324, 380],
|
||||
},
|
||||
A2: {
|
||||
2: [18.5, 25, 33, 42, 57, 76, 99, 121, 145, 183, 220, 253, 290, 329, 386],
|
||||
3: [16.5, 22, 30, 38, 51, 68, 89, 109, 130, 164, 197, 227, 259, 295, 346],
|
||||
},
|
||||
B1: {
|
||||
2: [23, 31, 42, 54, 75, 100, 133, 164, 198, 253, 306, 354, 393, 449, 528],
|
||||
3: [20, 28, 37, 48, 66, 88, 117, 144, 175, 222, 269, 312, 342, 384, 450],
|
||||
},
|
||||
B2: {
|
||||
2: [22, 30, 40, 51, 69, 91, 119, 146, 175, 221, 265, 305, 334, 384, 459],
|
||||
3: [19.5, 26, 35, 44, 60, 80, 105, 128, 154, 194, 233, 268, 300, 340, 398],
|
||||
},
|
||||
C: {
|
||||
2: [24, 33, 45, 58, 80, 107, 138, 171, 209, 269, 328, 382, 441, 506, 599],
|
||||
3: [22, 30, 40, 52, 71, 96, 119, 147, 179, 229, 278, 322, 371, 424, 500],
|
||||
},
|
||||
D1: {
|
||||
2: [25, 33, 43, 53, 71, 91, 116, 139, 164, 203, 239, 271, 306, 343, 395],
|
||||
3: [21, 28, 36, 44, 58, 75, 96, 115, 135, 167, 197, 223, 251, 281, 324],
|
||||
},
|
||||
D2: {
|
||||
2: [27, 35, 46, 58, 77, 100, 129, 155, 183, 225, 270, 306, 343, 387, 448],
|
||||
3: [23, 30, 39, 49, 65, 84, 107, 129, 153, 188, 226, 257, 287, 324, 375],
|
||||
},
|
||||
E: {
|
||||
2: [26, 36, 49, 63, 86, 115, 149, 185, 225, 289, 352, 410, 473, 542, 641],
|
||||
3: [23, 32, 42, 54, 75, 100, 127, 158, 192, 246, 298, 346, 399, 456, 538],
|
||||
},
|
||||
},
|
||||
aluminum: {
|
||||
// B.52.3 / B.52.5 aluminium; E: B.52.13.
|
||||
A1: {
|
||||
2: [n, 20, 27, 35, 48, 64, 84, 103, 125, 158, 191, 220, 253, 288, 338],
|
||||
3: [n, 19, 25, 32, 44, 58, 76, 94, 113, 142, 171, 197, 226, 256, 300],
|
||||
},
|
||||
A2: {
|
||||
2: [n, 19.5, 26, 33, 45, 60, 78, 96, 115, 145, 175, 201, 230, 262, 307],
|
||||
3: [n, 18, 24, 31, 41, 55, 71, 87, 104, 131, 157, 180, 206, 233, 273],
|
||||
},
|
||||
B1: {
|
||||
2: [n, 25, 33, 43, 59, 79, 105, 130, 157, 200, 242, 281, 307, 351, 412],
|
||||
3: [n, 22, 29, 38, 52, 71, 93, 116, 140, 179, 217, 251, 267, 300, 351],
|
||||
},
|
||||
B2: {
|
||||
2: [n, 23, 31, 40, 54, 72, 94, 115, 138, 175, 210, 242, 261, 300, 358],
|
||||
3: [n, 21, 28, 35, 48, 64, 84, 103, 124, 156, 188, 216, 240, 272, 318],
|
||||
},
|
||||
C: {
|
||||
2: [n, 26, 35, 45, 62, 84, 101, 126, 154, 198, 241, 280, 324, 371, 439],
|
||||
3: [n, 24, 32, 41, 57, 76, 90, 112, 136, 174, 211, 245, 283, 323, 382],
|
||||
},
|
||||
D1: {
|
||||
2: [n, 26, 33, 42, 55, 71, 90, 108, 128, 158, 186, 211, 238, 267, 307],
|
||||
3: [n, 22, 28, 35, 46, 59, 75, 90, 106, 130, 154, 174, 197, 220, 253],
|
||||
},
|
||||
D2: {
|
||||
2: [n, n, n, n, n, 76, 98, 117, 139, 170, 204, 233, 261, 296, 343],
|
||||
3: [n, n, n, n, n, 64, 82, 98, 117, 144, 172, 197, 220, 250, 290],
|
||||
},
|
||||
E: {
|
||||
2: [n, 28, 38, 49, 67, 91, 108, 135, 164, 211, 257, 300, 346, 397, 470],
|
||||
3: [n, 24, 32, 42, 58, 77, 97, 120, 146, 187, 227, 263, 304, 347, 409],
|
||||
},
|
||||
},
|
||||
},
|
||||
};
|
||||
|
||||
// -- Correction factors ------------------------------------------------------
|
||||
|
||||
/** B.52.14 (air, reference 30 °C) and B.52.15 (ground, reference 20 °C). */
|
||||
export const TEMPERATURE_FACTORS: Record<
|
||||
"air" | "ground",
|
||||
Record<InsulationMaterial, Record<number, number>>
|
||||
> = {
|
||||
air: {
|
||||
pvc: { 10: 1.22, 15: 1.17, 20: 1.12, 25: 1.06, 30: 1.0, 35: 0.94, 40: 0.87, 45: 0.79, 50: 0.71, 55: 0.61, 60: 0.5 },
|
||||
xlpe: {
|
||||
10: 1.15, 15: 1.12, 20: 1.08, 25: 1.04, 30: 1.0, 35: 0.96, 40: 0.91, 45: 0.87,
|
||||
50: 0.82, 55: 0.76, 60: 0.71, 65: 0.65, 70: 0.58, 75: 0.5, 80: 0.41,
|
||||
},
|
||||
},
|
||||
ground: {
|
||||
pvc: { 10: 1.1, 15: 1.05, 20: 1.0, 25: 0.95, 30: 0.89, 35: 0.84, 40: 0.77, 45: 0.71, 50: 0.63, 55: 0.55, 60: 0.45 },
|
||||
xlpe: {
|
||||
10: 1.07, 15: 1.04, 20: 1.0, 25: 0.96, 30: 0.93, 35: 0.89, 40: 0.85, 45: 0.8,
|
||||
50: 0.76, 55: 0.71, 60: 0.65, 65: 0.6, 70: 0.53, 75: 0.46, 80: 0.38,
|
||||
},
|
||||
},
|
||||
};
|
||||
|
||||
export const REFERENCE_TEMPERATURE_C: Record<"air" | "ground", number> = {
|
||||
air: 30,
|
||||
ground: 20,
|
||||
};
|
||||
|
||||
/**
|
||||
* Grouping reduction factors for touching circuits/cables:
|
||||
* air (A1–C, E): B.52.17 item 1 "bunched in air, on a surface, embedded or
|
||||
* enclosed" – the most restrictive arrangement, also used for E (single
|
||||
* layers on trays would allow higher factors);
|
||||
* D1: B.52.19 A (multi-core cables in touching ducts);
|
||||
* D2: B.52.18 (cables direct in ground, touching).
|
||||
*/
|
||||
export const GROUPING_FACTORS: Record<"air" | "D1" | "D2", Record<number, number>> = {
|
||||
air: { 1: 1.0, 2: 0.8, 3: 0.7, 4: 0.65, 5: 0.6, 6: 0.57, 7: 0.54, 8: 0.52, 9: 0.5, 12: 0.45, 16: 0.41, 20: 0.38 },
|
||||
D1: {
|
||||
1: 1.0, 2: 0.85, 3: 0.75, 4: 0.7, 5: 0.65, 6: 0.6, 7: 0.57, 8: 0.54, 9: 0.52, 10: 0.49,
|
||||
11: 0.47, 12: 0.45, 13: 0.44, 14: 0.42, 15: 0.41, 16: 0.39, 17: 0.38, 18: 0.37, 19: 0.35, 20: 0.34,
|
||||
},
|
||||
D2: { 1: 1.0, 2: 0.75, 3: 0.65, 4: 0.6, 5: 0.55, 6: 0.5, 7: 0.45, 8: 0.43, 9: 0.41, 12: 0.36, 16: 0.32, 20: 0.29 },
|
||||
};
|
||||
|
||||
export const MAX_GROUPING_CIRCUITS = 20;
|
||||
|
||||
function groupingTableFor(method: LayingMethod) {
|
||||
return method === "D1" ? GROUPING_FACTORS.D1 : method === "D2" ? GROUPING_FACTORS.D2 : GROUPING_FACTORS.air;
|
||||
}
|
||||
|
||||
/**
|
||||
* Looks up a tabulated factor. Values between tabulated keys use the next
|
||||
* higher key (the lower, safer factor); values above the table are not
|
||||
* supported (null) and values below the smallest key use the smallest key
|
||||
* (whose factor is lower than the true one, i.e. safe).
|
||||
*/
|
||||
function lookupConservative(table: Record<number, number>, value: number): { key: number; factor: number } | null {
|
||||
const keys = Object.keys(table).map(Number).sort((a, b) => a - b);
|
||||
const key = keys.find((candidate) => candidate >= value);
|
||||
if (key === undefined) {
|
||||
return null;
|
||||
}
|
||||
return { key, factor: table[key] };
|
||||
}
|
||||
|
||||
/** Tabulated temperatures offered by the UI for a laying method and insulation. */
|
||||
export function temperatureOptions(method: LayingMethod, insulation: InsulationMaterial): number[] {
|
||||
return Object.keys(TEMPERATURE_FACTORS[LAYING_METHOD_GROUP[method]][insulation])
|
||||
.map(Number)
|
||||
.sort((a, b) => a - b);
|
||||
}
|
||||
|
||||
// -- Conductor resistivity for the voltage drop -------------------------------
|
||||
|
||||
/** Conductivity in m/(Ω·mm²) at the maximum operating temperature (conservative). */
|
||||
export const KAPPA: Record<ConductorMaterial, number> = { copper: 48, aluminum: 30 };
|
||||
|
||||
// -- Practical minimum cross-sections by circuit category --------------------
|
||||
// A planning convention from docs/spec/06-future-sizing-and-calculations.md
|
||||
// ("Standard Single-Phase Circuits ... cable cross-section: 2.5 mm²"), not a
|
||||
// calculation result. It only ever raises a recommendation.
|
||||
export type CircuitCategory = "lighting" | "single_phase" | "three_phase";
|
||||
|
||||
export const PRACTICAL_MINIMUM_CROSS_SECTION_MM2: Partial<Record<CircuitCategory, number>> = {
|
||||
single_phase: 2.5,
|
||||
};
|
||||
|
||||
// -- Protective device --------------------------------------------------------
|
||||
|
||||
export const PROTECTION_KINDS = ["breaker", "fuse"] as const;
|
||||
export type ProtectionKind = (typeof PROTECTION_KINDS)[number];
|
||||
|
||||
export interface ExistingProtection {
|
||||
ratedCurrentA: number;
|
||||
/** breaker: circuit-breaker (I2 ≤ 1.45 In); fuse: gG fuse (I2 up to 2.1 In). */
|
||||
kind: ProtectionKind;
|
||||
}
|
||||
|
||||
/**
|
||||
* Conventional tripping/fusing current I2 as multiple of In.
|
||||
* Circuit-breakers (IEC 60898-1): 1.45. gG fuses (IEC 60269-2):
|
||||
* In ≤ 4 A: 2.1, 4 A < In < 16 A: 1.9, In ≥ 16 A: 1.6.
|
||||
*/
|
||||
export function conventionalTrippingFactor(protection: ExistingProtection): number {
|
||||
if (protection.kind === "breaker") {
|
||||
return 1.45;
|
||||
}
|
||||
if (protection.ratedCurrentA <= 4) {
|
||||
return 2.1;
|
||||
}
|
||||
return protection.ratedCurrentA < 16 ? 1.9 : 1.6;
|
||||
}
|
||||
|
||||
/**
|
||||
* Minimum Iz required by overload protection (IEC 60364-4-43, 433.1):
|
||||
* In ≤ Iz and I2 ≤ 1.45 · Iz.
|
||||
*/
|
||||
export function minimumIzForProtection(protection: ExistingProtection): number {
|
||||
return Math.max(
|
||||
protection.ratedCurrentA,
|
||||
(conventionalTrippingFactor(protection) * protection.ratedCurrentA) / 1.45
|
||||
);
|
||||
}
|
||||
|
||||
// -- Input / result -----------------------------------------------------------
|
||||
|
||||
export interface CableSizingInput {
|
||||
phase: 1 | 3;
|
||||
mode: "power" | "current";
|
||||
/** kW, only used when mode === "power" */
|
||||
powerKw?: number;
|
||||
/** A, only used when mode === "current" */
|
||||
currentA?: number;
|
||||
cosPhi: number;
|
||||
/** Line voltage in V (project single-/three-phase voltage). */
|
||||
voltage: number;
|
||||
/** Single-run cable length in m. */
|
||||
lengthM: number;
|
||||
layingMethod: LayingMethod;
|
||||
conductorMaterial: ConductorMaterial;
|
||||
insulation: InsulationMaterial;
|
||||
/** Ambient air temperature, or ground temperature for D1/D2. */
|
||||
ambientTemperatureC: number;
|
||||
/** Number of grouped circuits or multi-core cables, including this one. */
|
||||
groupingCircuits: number;
|
||||
maxVoltageDropPercent: number;
|
||||
harmonicNeutralLoad: HarmonicNeutralLoad;
|
||||
existingProtection?: ExistingProtection;
|
||||
circuitCategory?: CircuitCategory;
|
||||
}
|
||||
|
||||
export interface CrossSectionRow {
|
||||
crossSectionMm2: number;
|
||||
/** Tabulated Iz; null if the table has no value for this size. */
|
||||
ratedCurrentA: number | null;
|
||||
correctedCurrentA: number | null;
|
||||
currentSufficient: boolean | null;
|
||||
voltageDropPercent: number | null;
|
||||
voltageDropSufficient: boolean | null;
|
||||
/** Longest single run meeting maxVoltageDropPercent at this load. */
|
||||
maxLengthForVoltageDropM: number | null;
|
||||
recommended: boolean;
|
||||
}
|
||||
|
||||
export interface ProtectionCoordinationResult {
|
||||
ratedCurrentA: number;
|
||||
kind: ProtectionKind;
|
||||
/** I2 / In used for the check. */
|
||||
conventionalTrippingFactor: number;
|
||||
/** In ≤ Iz and I2 ≤ 1.45 · Iz for the recommended cross-section. */
|
||||
coordinated: boolean;
|
||||
}
|
||||
|
||||
export type UnsupportedReason = "temperature" | "grouping";
|
||||
|
||||
export interface CableSizingResult {
|
||||
/** false: the inputs are outside the tabulated range – no numeric result. */
|
||||
supported: boolean;
|
||||
unsupportedReason: UnsupportedReason | null;
|
||||
operatingCurrentA: number;
|
||||
/**
|
||||
* Current the cross-section must carry after correction:
|
||||
* max(Ib, In, I2/1.45) with an existing protective device, otherwise Ib.
|
||||
*/
|
||||
designCurrentA: number;
|
||||
/** Tabulated temperature/grouping actually used (rounded to the safe side). */
|
||||
temperatureUsedC: number | null;
|
||||
groupingUsed: number | null;
|
||||
temperatureFactor: number | null;
|
||||
groupingFactor: number | null;
|
||||
crossSectionByCapacityMm2: number | null;
|
||||
crossSectionByVoltageDropMm2: number | null;
|
||||
recommendedCrossSectionMm2: number | null;
|
||||
voltageDropAtRecommendedPercent: number | null;
|
||||
combinedDerationFactor: number;
|
||||
harmonicReductionApplied: boolean;
|
||||
practicalMinimumApplied: boolean;
|
||||
rows: CrossSectionRow[];
|
||||
protectionCoordination: ProtectionCoordinationResult | null;
|
||||
}
|
||||
|
||||
function operatingCurrentA(input: CableSizingInput): number {
|
||||
if (input.mode === "current") {
|
||||
return input.currentA ?? 0;
|
||||
}
|
||||
const powerW = (input.powerKw ?? 0) * 1000;
|
||||
return input.phase === 1
|
||||
? powerW / (input.voltage * input.cosPhi)
|
||||
: powerW / (Math.sqrt(3) * input.voltage * input.cosPhi);
|
||||
}
|
||||
|
||||
export function calculateCableSizing(input: CableSizingInput): CableSizingResult {
|
||||
const ib = operatingCurrentA(input);
|
||||
const designCurrentA = input.existingProtection
|
||||
? Math.max(ib, minimumIzForProtection(input.existingProtection))
|
||||
: ib;
|
||||
const group = LAYING_METHOD_GROUP[input.layingMethod];
|
||||
const temperature = lookupConservative(
|
||||
TEMPERATURE_FACTORS[group][input.insulation],
|
||||
input.ambientTemperatureC
|
||||
);
|
||||
const grouping =
|
||||
input.groupingCircuits <= MAX_GROUPING_CIRCUITS
|
||||
? lookupConservative(groupingTableFor(input.layingMethod), Math.max(1, input.groupingCircuits))
|
||||
: null;
|
||||
|
||||
const empty: CableSizingResult = {
|
||||
supported: false,
|
||||
unsupportedReason: !temperature ? "temperature" : "grouping",
|
||||
operatingCurrentA: ib,
|
||||
designCurrentA,
|
||||
temperatureUsedC: temperature?.key ?? null,
|
||||
groupingUsed: grouping?.key ?? null,
|
||||
temperatureFactor: temperature?.factor ?? null,
|
||||
groupingFactor: grouping?.factor ?? null,
|
||||
crossSectionByCapacityMm2: null,
|
||||
crossSectionByVoltageDropMm2: null,
|
||||
recommendedCrossSectionMm2: null,
|
||||
voltageDropAtRecommendedPercent: null,
|
||||
combinedDerationFactor: 1,
|
||||
harmonicReductionApplied: false,
|
||||
practicalMinimumApplied: false,
|
||||
rows: [],
|
||||
protectionCoordination: null,
|
||||
};
|
||||
if (!temperature || !grouping) {
|
||||
return empty;
|
||||
}
|
||||
|
||||
const coreCount: CoreCount = input.phase === 1 ? 2 : 3;
|
||||
const harmonicReductionApplied =
|
||||
input.phase === 3 && input.harmonicNeutralLoad === "15to33Percent";
|
||||
const combinedDerationFactor =
|
||||
temperature.factor * grouping.factor * (harmonicReductionApplied ? HARMONIC_REDUCTION_FACTOR : 1);
|
||||
const voltageDropCoefficient = input.phase === 1 ? 2 : Math.sqrt(3);
|
||||
const kappa = KAPPA[input.conductorMaterial];
|
||||
|
||||
const ratedCurrents =
|
||||
CURRENT_CAPACITY_A[input.insulation][input.conductorMaterial][input.layingMethod][coreCount];
|
||||
const correctedCurrents = ratedCurrents.map((value) =>
|
||||
value == null ? null : value * combinedDerationFactor
|
||||
);
|
||||
const voltageDrops = CROSS_SECTIONS_MM2.map(
|
||||
(crossSection) =>
|
||||
((voltageDropCoefficient * input.lengthM * ib * input.cosPhi) / (kappa * crossSection) / input.voltage) * 100
|
||||
);
|
||||
|
||||
const indexByCapacity = correctedCurrents.findIndex(
|
||||
(value) => value != null && value >= designCurrentA
|
||||
);
|
||||
const indexByVoltageDrop = voltageDrops.findIndex(
|
||||
(value, index) => ratedCurrents[index] != null && value <= input.maxVoltageDropPercent
|
||||
);
|
||||
let indexRecommended =
|
||||
indexByCapacity >= 0 && indexByVoltageDrop >= 0 ? Math.max(indexByCapacity, indexByVoltageDrop) : -1;
|
||||
|
||||
const practicalMinimumMm2 = input.circuitCategory
|
||||
? PRACTICAL_MINIMUM_CROSS_SECTION_MM2[input.circuitCategory]
|
||||
: undefined;
|
||||
let practicalMinimumApplied = false;
|
||||
if (indexRecommended >= 0 && practicalMinimumMm2 != null && CROSS_SECTIONS_MM2[indexRecommended] < practicalMinimumMm2) {
|
||||
const minimumIndex = CROSS_SECTIONS_MM2.indexOf(practicalMinimumMm2 as (typeof CROSS_SECTIONS_MM2)[number]);
|
||||
if (minimumIndex >= 0 && ratedCurrents[minimumIndex] != null) {
|
||||
indexRecommended = minimumIndex;
|
||||
practicalMinimumApplied = true;
|
||||
}
|
||||
}
|
||||
|
||||
const voltageDropCurrentBasis = ib * input.cosPhi;
|
||||
const rows: CrossSectionRow[] = CROSS_SECTIONS_MM2.map((crossSection, index) => {
|
||||
const rated = ratedCurrents[index];
|
||||
const corrected = correctedCurrents[index];
|
||||
return {
|
||||
crossSectionMm2: crossSection,
|
||||
ratedCurrentA: rated,
|
||||
correctedCurrentA: corrected,
|
||||
currentSufficient: corrected == null ? null : corrected >= designCurrentA,
|
||||
voltageDropPercent: rated == null ? null : voltageDrops[index],
|
||||
voltageDropSufficient: rated == null ? null : voltageDrops[index] <= input.maxVoltageDropPercent,
|
||||
maxLengthForVoltageDropM:
|
||||
rated == null || voltageDropCurrentBasis <= 0
|
||||
? null
|
||||
: (input.maxVoltageDropPercent * kappa * crossSection * input.voltage) /
|
||||
(100 * voltageDropCoefficient * voltageDropCurrentBasis),
|
||||
recommended: index === indexRecommended,
|
||||
};
|
||||
});
|
||||
|
||||
let protectionCoordination: ProtectionCoordinationResult | null = null;
|
||||
if (input.existingProtection && indexRecommended >= 0) {
|
||||
const iz = rows[indexRecommended].correctedCurrentA;
|
||||
const factor = conventionalTrippingFactor(input.existingProtection);
|
||||
const inA = input.existingProtection.ratedCurrentA;
|
||||
protectionCoordination = {
|
||||
ratedCurrentA: inA,
|
||||
kind: input.existingProtection.kind,
|
||||
conventionalTrippingFactor: factor,
|
||||
coordinated: iz != null && inA <= iz && factor * inA <= 1.45 * iz,
|
||||
};
|
||||
}
|
||||
|
||||
return {
|
||||
...empty,
|
||||
supported: true,
|
||||
unsupportedReason: null,
|
||||
crossSectionByCapacityMm2: indexByCapacity >= 0 ? CROSS_SECTIONS_MM2[indexByCapacity] : null,
|
||||
crossSectionByVoltageDropMm2: indexByVoltageDrop >= 0 ? CROSS_SECTIONS_MM2[indexByVoltageDrop] : null,
|
||||
recommendedCrossSectionMm2: indexRecommended >= 0 ? CROSS_SECTIONS_MM2[indexRecommended] : null,
|
||||
voltageDropAtRecommendedPercent: indexRecommended >= 0 ? voltageDrops[indexRecommended] : null,
|
||||
combinedDerationFactor,
|
||||
harmonicReductionApplied,
|
||||
practicalMinimumApplied,
|
||||
rows,
|
||||
protectionCoordination,
|
||||
};
|
||||
}
|
||||
|
||||
// -- Alerts -------------------------------------------------------------------
|
||||
|
||||
export interface CableSizingAlert {
|
||||
kind: "critical" | "warn" | "info" | "ok";
|
||||
text: string;
|
||||
}
|
||||
|
||||
const numberFormat = (value: number, digits = 1) =>
|
||||
value.toLocaleString("de-DE", { minimumFractionDigits: digits, maximumFractionDigits: digits });
|
||||
const crossSectionFormat = (value: number) =>
|
||||
`${value.toLocaleString("de-DE", { maximumFractionDigits: 1 })} mm²`;
|
||||
|
||||
export function buildCableSizingAlerts(input: CableSizingInput, result: CableSizingResult): CableSizingAlert[] {
|
||||
const alerts: CableSizingAlert[] = [];
|
||||
const group = LAYING_METHOD_GROUP[input.layingMethod];
|
||||
|
||||
if (!result.supported) {
|
||||
alerts.push({
|
||||
kind: "critical",
|
||||
text:
|
||||
result.unsupportedReason === "temperature"
|
||||
? `${group === "air" ? "Umgebungstemperatur" : "Bodentemperatur"} ${input.ambientTemperatureC} °C liegt außerhalb der Tabelle für ${input.insulation === "pvc" ? "PVC" : "VPE"} – keine Berechnung möglich.`
|
||||
: `Häufung mit ${input.groupingCircuits} Stromkreisen liegt außerhalb der Tabelle (max. ${MAX_GROUPING_CIRCUITS}) – keine Berechnung möglich.`,
|
||||
});
|
||||
return alerts;
|
||||
}
|
||||
|
||||
if (result.temperatureUsedC !== input.ambientTemperatureC) {
|
||||
alerts.push({
|
||||
kind: "info",
|
||||
text: `Temperatur auf den nächsten Tabellenwert ${result.temperatureUsedC} °C gerundet (sichere Seite).`,
|
||||
});
|
||||
}
|
||||
if (result.groupingUsed !== input.groupingCircuits) {
|
||||
alerts.push({
|
||||
kind: "info",
|
||||
text: `Häufung auf den nächsten Tabellenwert ${result.groupingUsed} Stromkreise gerundet (sichere Seite).`,
|
||||
});
|
||||
}
|
||||
|
||||
const byCapacity = result.crossSectionByCapacityMm2;
|
||||
const byDrop = result.crossSectionByVoltageDropMm2;
|
||||
if (byCapacity == null) {
|
||||
const dueToProtection =
|
||||
input.existingProtection != null && result.designCurrentA > result.operatingCurrentA;
|
||||
alerts.push({
|
||||
kind: "critical",
|
||||
text: dueToProtection
|
||||
? `Das vorhandene Schutzorgan (${input.existingProtection!.ratedCurrentA} A) verlangt Iz ≥ ${numberFormat(result.designCurrentA)} A – das erreicht bei Verlegeart ${input.layingMethod} kein Querschnitt bis 240 mm². Verlegeart oder Schutzorgan prüfen.`
|
||||
: `Der Betriebsstrom ${numberFormat(result.operatingCurrentA)} A übersteigt bei Verlegeart ${input.layingMethod} die Belastbarkeit aller Querschnitte bis 240 mm².`,
|
||||
});
|
||||
} else if (byDrop == null) {
|
||||
alerts.push({
|
||||
kind: "critical",
|
||||
text: `Der Spannungsfall von ${numberFormat(input.maxVoltageDropPercent)} % wird bei ${input.lengthM} m mit keinem Querschnitt bis 240 mm² eingehalten.`,
|
||||
});
|
||||
} else if (byDrop > byCapacity) {
|
||||
alerts.push({
|
||||
kind: "warn",
|
||||
text: `Der Spannungsfall ist maßgeblich: ${crossSectionFormat(byCapacity)} reichen thermisch, für ΔU ≤ ${numberFormat(input.maxVoltageDropPercent)} % sind ${crossSectionFormat(byDrop)} nötig.`,
|
||||
});
|
||||
}
|
||||
if (result.harmonicReductionApplied) {
|
||||
alerts.push({
|
||||
kind: "info",
|
||||
text: "Reduktionsfaktor 0,86 wegen 15–33 % 3. Harmonischer im Neutralleiter angewendet.",
|
||||
});
|
||||
}
|
||||
if (input.phase === 3 && input.harmonicNeutralLoad === "over33Percent") {
|
||||
alerts.push({
|
||||
kind: "warn",
|
||||
text: "3. Harmonische > 33 %: Der Neutralleiter ist nach dem Neutralleiterstrom zu bemessen – hier nicht berücksichtigt.",
|
||||
});
|
||||
}
|
||||
if (group === "ground") {
|
||||
alerts.push({
|
||||
kind: "info",
|
||||
text: "Erdverlegung: Bodenwärmewiderstand 2,5 K·m/W angenommen (Tabellenreferenz).",
|
||||
});
|
||||
}
|
||||
if (result.practicalMinimumApplied) {
|
||||
alerts.push({
|
||||
kind: "info",
|
||||
text: `Auf ${crossSectionFormat(result.recommendedCrossSectionMm2!)} angehoben (Praxis-Mindestquerschnitt für 1-phasige Stromkreise, keine Rechenanforderung).`,
|
||||
});
|
||||
}
|
||||
if (result.protectionCoordination) {
|
||||
const coordination = result.protectionCoordination;
|
||||
const kindLabel = coordination.kind === "breaker" ? "Leitungsschutzschalter" : "Sicherung gG";
|
||||
alerts.push(
|
||||
coordination.coordinated
|
||||
? {
|
||||
kind: "info",
|
||||
text: `Schutzorgan ${kindLabel} ${coordination.ratedCurrentA} A berücksichtigt: In ≤ Iz und I₂ = ${numberFormat(coordination.conventionalTrippingFactor, 2)} · In ≤ 1,45 · Iz. Kurzschlussschutz und Abschaltbedingungen sind nicht Teil dieser Berechnung.`,
|
||||
}
|
||||
: {
|
||||
kind: "warn",
|
||||
text: `Schutzorgan ${kindLabel} ${coordination.ratedCurrentA} A ist mit dem empfohlenen Querschnitt nicht koordiniert (In ≤ Iz, I₂ ≤ 1,45 · Iz).`,
|
||||
}
|
||||
);
|
||||
}
|
||||
const recommendedRow = result.rows.find((row) => row.recommended);
|
||||
if (recommendedRow && byCapacity != null && byDrop != null) {
|
||||
if (!alerts.some((alert) => alert.kind === "warn" || alert.kind === "critical")) {
|
||||
alerts.push({
|
||||
kind: "ok",
|
||||
text: `${crossSectionFormat(recommendedRow.crossSectionMm2)} ${input.conductorMaterial === "aluminum" ? "Al" : "Cu"} erfüllt bei ${input.lengthM} m Belastbarkeit (${numberFormat(result.designCurrentA)} A) und Spannungsfall (ΔU ≤ ${numberFormat(input.maxVoltageDropPercent)} %).`,
|
||||
});
|
||||
}
|
||||
if (recommendedRow.maxLengthForVoltageDropM != null) {
|
||||
alerts.push({
|
||||
kind: "info",
|
||||
text: `Maximale Länge bei ${crossSectionFormat(recommendedRow.crossSectionMm2)} für ΔU ≤ ${numberFormat(input.maxVoltageDropPercent)} %: ${recommendedRow.maxLengthForVoltageDropM.toFixed(0)} m.`,
|
||||
});
|
||||
}
|
||||
}
|
||||
return alerts;
|
||||
}
|
||||
Loading…
Add table
Add a link
Reference in a new issue