Align cable sizing with DIN VDE 0298-4
This commit is contained in:
parent
598003554a
commit
5cbbd3a84a
9 changed files with 262 additions and 244 deletions
|
|
@ -20,11 +20,11 @@
|
|||
- The global device library supports basic CRUD and copy operations, but has no
|
||||
versioning, permissions or controlled synchronization model.
|
||||
- There is no automatic sizing of all circuits. The optional cable sizing
|
||||
module suggests a cross-section for one circuit on demand (IEC 60364-5-52
|
||||
Annex B tables; no short-circuit, disconnection-time or selectivity checks,
|
||||
no methods F/G, soil resistivity fixed at 2.5 K·m/W) and does not validate
|
||||
manually entered cable values. National tables (DIN VDE 0298-4) must be
|
||||
checked by the planner; see `docs/cable-sizing-module.md`.
|
||||
module suggests a cross-section for one circuit on demand using
|
||||
DIN VDE 0298-4:2023-06 with Berichtigung 1:2023-10. It excludes direct
|
||||
burial, grouped method E and neutral-current sizing above 33 % third
|
||||
harmonic, and it does not check short-circuit withstand, disconnection time
|
||||
or selectivity. See `docs/cable-sizing-module.md`.
|
||||