Author SHA1 Message Date
573487666c Integrate rough estimate balance 2026-09-27 12:37:59 +02:00
Grovy311
72189d23a5 Offer supply suggestions, drop the circuit column, center cells
The Versorgung field suggests ELT and MSR (plus values already used in
the balance) through a datalist and still accepts free text. The circuit
number column is not needed in early design phases; it is removed from
the data model, the regenerated migration 0010, the editor and the
print. All cells are centered except "Verbraucher / Flächen", group
titles and total labels.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-26 17:56:53 +02:00
Grovy311
37a70b6b36 Add the rough power balance module for early design phases
In LPH 2/3 there are no circuits yet, but the office needs a power
balance by DIN 276 cost group, as in the Excel template "Leistungsbilanz -
KG400": each trade enters consumers by piece or by area (W/m²) with GLF
and cos phi; the balance sums AV and SV per cost group, adds a reserve and
derives the maximum current.

The module is separate from the circuit structure: own tables
(migration 0010), own folder src/estimate-balance and an import-free
shared calculation used by API and UI. Writes go through project commands
(estimate-balance.insert/.update/.delete with complete documents), so
revision checks and Undo/Redo apply; it is not part of project snapshots
or transfer yet. A comparison endpoint sums the device rows of all circuit
lists by cost group (longest prefix) against the estimate.

The UI adds a sidebar entry, a list of Stände (template KG 400, empty or
copy) and a spreadsheet-like editor with autosave, AMEV picker for the
GLF, totals, reserve, maximum current, comparison table and print layout.
The tests reproduce the template example exactly (143.24 kW, 148.48 kVA,
157.56 kW / 163.33 kVA with 10 % reserve, 235.75 A). See
docs/estimate-balance.md and issue #7.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-26 17:39:28 +02:00