Commit graph

48 commits

Author SHA1 Message Date
Grovy311
49488f4e1b Add optional cable-sizing module
Per-circuit cross-section recommendation as a separate module attached to
the circuit list. It never writes project data itself: "Übernehmen" applies
cable type, cross-section and length through the regular circuit.update
command, so revisions and Undo/Redo stay intact.

- Pure domain module (src/cable-sizing) with IEC 60364-5-52:2009 Annex B
  tables for PVC and XLPE, copper and aluminium, methods A1, A2, B1, B2, C,
  D1, D2 and E. Every value was cross-checked against public reproductions;
  where sources differ the lower value is used (docs/cable-sizing-module.md).
- Temperature and grouping between table values round to the safer value;
  values outside the tables return no result instead of a factor of 1.
  Ground methods use B.52.18 (D2) and B.52.19 A (D1).
- Overload protection: circuit-breakers In <= Iz; gG fuses additionally
  I2 <= 1.45 Iz with I2 = 1.6/1.9/2.1 In.
- Inputs prefilled from the circuit: power, phase (group or device rows),
  project voltage, power-weighted cos phi, length and protective device.
- Opened from a "Leitungsberechnung" button in the row actions, not from a
  grid cell, so cable cells keep the spreadsheet behavior.
- Stateless API under /api/cable-sizing; no database table or migration.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-26 11:16:18 +02:00
a99980c47b Update docs for the code-review fixes
- circuit-list-editor-api.md: next-identifier moved under
  /projects/:projectId and now documents its 404 scoping behavior.
- current-architecture.md: clarify that the BMK trigger register's
  DB-level normalization is ASCII-only and describe the added
  application-level Unicode-aware uniqueness check that closes the
  umlaut gap; note the additive migration 0006 indexes.

Co-Authored-By: Claude Sonnet 5 <noreply@anthropic.com>
2026-08-06 21:33:28 +02:00
74bea1a3c9 Add Revit circuit list object feed 2026-08-02 18:59:01 +02:00
ab2449419b Add Revit initial import wizard 2026-08-02 17:52:21 +02:00
caa6caf99f Add Revit CSV preview API 2026-08-02 16:49:42 +02:00
44b6fde940 Add public building project setting 2026-07-31 17:41:30 +02:00
43a3bb0b69 Align documentation with clean baseline 2026-07-31 16:41:37 +02:00
1eed19ef6b Add editable project floors and rooms 2026-07-31 14:46:06 +02:00
734a2bcfc4 Create clean release database baseline 2026-07-31 14:07:26 +02:00
5bee3cb103 Add distribution board copy and delete controls 2026-07-31 12:03:52 +02:00
7c8d4a7ddf Document protected circuit groups 2026-07-31 08:06:10 +02:00
7a9530a914 Expose protected tree structure 2026-07-30 20:14:45 +02:00
9d4d4082fe Create protected board defaults 2026-07-30 19:30:53 +02:00
084103bf54 Derive device voltages from project settings 2026-07-29 09:53:58 +02:00
b1a11397b3 Add configurable distribution supply types 2026-07-29 09:31:20 +02:00
ac465a1cc0 Persist project locations 2026-07-26 10:56:29 +02:00
1cf26a932e Persist distribution board setup 2026-07-25 23:41:27 +02:00
1a77eedaa8 Add automatic project snapshots 2026-07-25 23:27:51 +02:00
b2763f72d5 Persist project settings updates 2026-07-25 23:08:07 +02:00
384a5769ab Restore named project snapshots 2026-07-25 22:41:24 +02:00
7c670fece3 Add named project snapshots 2026-07-25 22:15:22 +02:00
5a0c9019af Expose project revision timeline 2026-07-25 21:57:03 +02:00
c45afd0981 Persist section renumbering 2026-07-25 21:30:29 +02:00
abcb468807 Persist circuit reorders 2026-07-25 21:22:10 +02:00
08a2775a88 Persist device row moves 2026-07-25 21:09:02 +02:00
2eba4ea75e Persist circuit structure edits 2026-07-25 20:49:34 +02:00
76d8d59391 Persist circuit cell edits 2026-07-25 20:26:45 +02:00
3977a6e6e1 Persist project device synchronization 2026-07-24 11:47:03 +02:00
e930cb75b8 Route project devices through history 2026-07-24 10:57:50 +02:00
ac16cca77a Add project device structure history 2026-07-24 09:09:59 +02:00
0bc6c7372f Add project device update history 2026-07-24 08:57:57 +02:00
2668fc2f16 Add project device sync history 2026-07-24 08:47:25 +02:00
4b4603b71b Add section renumber history 2026-07-24 08:34:31 +02:00
332dfdb5d9 Add circuit reorder history 2026-07-24 08:21:32 +02:00
53282e8c7c Add placeholder move history 2026-07-23 22:39:59 +02:00
0a51703315 Add device row move history 2026-07-23 22:29:44 +02:00
ca13efbfcb Add circuit history commands 2026-07-23 22:18:36 +02:00
bd5f4f925f Add device row history commands 2026-07-23 22:09:53 +02:00
e4c7cf06e9 Add project command API 2026-07-23 21:56:13 +02:00
1e4dd26bb8 Add persistent history stacks 2026-07-23 21:48:24 +02:00
903d977443 Add project revision foundation 2026-07-23 21:17:48 +02:00
6b6d2c2a42 Rewrite project documentation 2026-07-23 21:05:43 +02:00
3fbf3ac622 Remove legacy consumer API 2026-07-23 20:00:48 +02:00
b2034c7dfb Create distribution boards atomically 2026-07-23 17:45:33 +02:00
0800f984bb Create circuits with rows atomically 2026-07-23 17:36:38 +02:00
b2f5ce77a5 Make device sync atomic and undoable 2026-07-22 19:47:10 +02:00
6f8b292b6b Add explicit project device sync 2026-07-22 19:38:21 +02:00
7580ad0ade Documentation 2026-05-07 22:55:15 +02:00