# Future Sizing and Calculation Requirements
|
||||
|
||||
These requirements are not part of the first implementation, but the structure should support them.
|
||||
|
||||
## Goal
|
||||
|
||||
The app should later support rule-based protection and cable sizing.
|
||||
|
||||
Future suggestions or checks may include:
|
||||
|
||||
- protection device type
|
||||
- rated current
|
||||
- tripping characteristic
|
||||
- cable type
|
||||
- number of cores
|
||||
- cable cross-section
|
||||
- minimum cable cross-section based on current
|
||||
- maximum permissible cable length based on voltage drop
|
||||
- warning messages if cable length, cross-section or protection device do not match
|
||||
|
||||
Users must remain able to manually override suggestions.
|
||||
|
||||
## Initial Design Rule Examples
|
||||
|
||||
These are common planning defaults, not a replacement for full norm-compliant calculation.
|
||||
|
||||
### Lighting Circuits
|
||||
|
||||
Lighting circuits in section `-1Fx` usually use:
|
||||
|
||||
- protection rated current: 10 A
|
||||
- cable cross-section: 1.5 mm²
|
||||
|
||||
Typical cable type:
|
||||
|
||||
- non-DALI lighting: 3x1.5 mm²
|
||||
- DALI-capable lighting: 5x1.5 mm²
|
||||
|
||||
The app should later suggest the cable type based on whether the connected luminaires require DALI or additional control cores.
|
||||
|
||||
### Standard Single-Phase Circuits
|
||||
|
||||
Standard single-phase circuits in section `-2Fx` usually use:
|
||||
|
||||
- protection rated current: 16 A
|
||||
- cable cross-section: 2.5 mm²
|
||||
|
||||
This applies to many typical socket circuits and standard single-phase loads.
|
||||
|
||||
### Special Loads and Long Cable Runs
|
||||
|
||||
For non-standard loads or long cable runs, voltage drop becomes more important.
|
||||
|
||||
Examples:
|
||||
|
||||
- instantaneous water heaters
|
||||
- socket combinations with higher connected load
|
||||
- outdoor circuits with long cable routes
|
||||
- lighting circuits with looped-through luminaires and cable lengths of 80 to 100 m
|
||||
|
||||
The app should later show warnings or require review if voltage drop becomes critical.
|
||||
|
||||
## Future Field: Control Requirement
|
||||
|
||||
To support cable suggestions for lighting circuits, devices or circuits may later include a control requirement.
|
||||
|
||||
Example values:
|
||||
|
||||
- none
|
||||
- DALI
|
||||
- KNX
|
||||
- switched only
|
||||
- dimmable
|
||||
- other
|
||||
|
||||
For lighting circuits:
|
||||
|
||||
- no additional control cores: suggest 3x1.5 mm²
|
||||
- DALI required: suggest 5x1.5 mm²
|
||||
|
||||
This must be configurable and manually overridable.
|
||||
|
||||
## Future Voltage Drop Check
|
||||
|
||||
A future voltage drop check may use:
|
||||
|
||||
- phase type
|
||||
- voltage
|
||||
- circuit total power
|
||||
- apparent power or current
|
||||
- cable material
|
||||
- cable cross-section
|
||||
- cable length
|
||||
- protection rated current
|
||||
- allowed voltage drop
|
||||
|
||||
The result should be shown as a warning or status indicator, not as an automatic forced change.
|
||||