Add optional cable-sizing module

Per-circuit cross-section recommendation as a separate module attached to
the circuit list. It never writes project data itself: "Übernehmen" applies
cable type, cross-section and length through the regular circuit.update
command, so revisions and Undo/Redo stay intact.

- Pure domain module (src/cable-sizing) with IEC 60364-5-52:2009 Annex B
  tables for PVC and XLPE, copper and aluminium, methods A1, A2, B1, B2, C,
  D1, D2 and E. Every value was cross-checked against public reproductions;
  where sources differ the lower value is used (docs/cable-sizing-module.md).
- Temperature and grouping between table values round to the safer value;
  values outside the tables return no result instead of a factor of 1.
  Ground methods use B.52.18 (D2) and B.52.19 A (D1).
- Overload protection: circuit-breakers In <= Iz; gG fuses additionally
  I2 <= 1.45 Iz with I2 = 1.6/1.9/2.1 In.
- Inputs prefilled from the circuit: power, phase (group or device rows),
  project voltage, power-weighted cos phi, length and protective device.
- Opened from a "Leitungsberechnung" button in the row actions, not from a
  grid cell, so cable cells keep the spreadsheet behavior.
- Stateless API under /api/cable-sizing; no database table or migration.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
This commit is contained in:
Grovy311 2026-09-26 10:59:41 +02:00
parent d95f0bf5c0
commit 49488f4e1b
17 changed files with 1999 additions and 4 deletions

View file

@ -17,8 +17,12 @@
- Persistence currently targets local SQLite; PostgreSQL is an architectural option, not an implemented runtime.
- The global device library supports basic CRUD and copy operations, but has no
versioning, permissions or controlled synchronization model.
- Final electrical sizing logic is not implemented yet.
- No full norm-compliant voltage-drop and protection-dimensioning calculation flow yet.
- There is no automatic sizing of all circuits. The optional cable sizing
module suggests a cross-section for one circuit on demand (IEC 60364-5-52
Annex B tables; no short-circuit, disconnection-time or selectivity checks,
no methods F/G, soil resistivity fixed at 2.5 K·m/W) and does not validate
manually entered cable values. National tables (DIN VDE 0298-4) must be
checked by the planner; see `docs/cable-sizing-module.md`.