Align cable sizing with DIN VDE 0298-4

This commit is contained in:
Julian Appel 2026-09-27 17:01:23 +02:00
parent 598003554a
commit 5cbbd3a84a
9 changed files with 262 additions and 244 deletions

View file

@ -607,10 +607,13 @@ circuit list (see `docs/cable-sizing-module.md`). Rules:
by clicking a grid cell; cable cells keep the normal spreadsheet behavior.
- It has no database table and no migration; `/api/cable-sizing/*` is
stateless.
- Reference data is IEC 60364-5-52:2009 Annex B. Change table values only with
a documented source in `docs/cable-sizing-module.md`; where sources differ,
use the lower value. Inputs outside the tables return no result instead of
assuming a factor of 1.
- Current-carrying capacities and correction factors use
DIN VDE 0298-4:2023-06 with Berichtigung 1:2023-10; the exact scope and the
separate basis of voltage-drop and protection checks are documented in
`docs/cable-sizing-module.md`. Inputs outside the supported tables return no
result instead of assuming a factor of 1. Direct burial, grouped method E,
aluminium below 25 mm² and neutral-current sizing above 33 % third harmonic
remain unsupported until their required inputs or normative basis exist.
- Inputs are prefilled from the circuit (power, phase, voltage, weighted cos φ,
length, protective device) and remain editable; manual cable entry without
a calculation stays possible.