Align cable sizing with DIN VDE 0298-4
This commit is contained in:
parent
598003554a
commit
5cbbd3a84a
9 changed files with 262 additions and 244 deletions
11
AGENTS.md
11
AGENTS.md
|
|
@ -607,10 +607,13 @@ circuit list (see `docs/cable-sizing-module.md`). Rules:
|
|||
by clicking a grid cell; cable cells keep the normal spreadsheet behavior.
|
||||
- It has no database table and no migration; `/api/cable-sizing/*` is
|
||||
stateless.
|
||||
- Reference data is IEC 60364-5-52:2009 Annex B. Change table values only with
|
||||
a documented source in `docs/cable-sizing-module.md`; where sources differ,
|
||||
use the lower value. Inputs outside the tables return no result instead of
|
||||
assuming a factor of 1.
|
||||
- Current-carrying capacities and correction factors use
|
||||
DIN VDE 0298-4:2023-06 with Berichtigung 1:2023-10; the exact scope and the
|
||||
separate basis of voltage-drop and protection checks are documented in
|
||||
`docs/cable-sizing-module.md`. Inputs outside the supported tables return no
|
||||
result instead of assuming a factor of 1. Direct burial, grouped method E,
|
||||
aluminium below 25 mm² and neutral-current sizing above 33 % third harmonic
|
||||
remain unsupported until their required inputs or normative basis exist.
|
||||
- Inputs are prefilled from the circuit (power, phase, voltage, weighted cos φ,
|
||||
length, protective device) and remain editable; manual cable entry without
|
||||
a calculation stays possible.
|
||||
|
|
|
|||