Commit graph

58 commits

Author SHA1 Message Date
9165b8238c Compact single-board feeder circuit rows 2026-09-28 22:14:39 +02:00
b74b495fab Update print view and documentation for logical feeds 2026-09-28 20:57:58 +02:00
dce31ee143 Add optional room areas 2026-09-27 20:00:03 +02:00
5cbbd3a84a Align cable sizing with DIN VDE 0298-4 2026-09-27 17:01:23 +02:00
598003554a Merge remote-tracking branch 'origin/main' into feature/cable-sizing 2026-09-27 16:54:12 +02:00
573487666c Integrate rough estimate balance 2026-09-27 12:37:59 +02:00
Grovy311
37a70b6b36 Add the rough power balance module for early design phases
In LPH 2/3 there are no circuits yet, but the office needs a power
balance by DIN 276 cost group, as in the Excel template "Leistungsbilanz -
KG400": each trade enters consumers by piece or by area (W/m²) with GLF
and cos phi; the balance sums AV and SV per cost group, adds a reserve and
derives the maximum current.

The module is separate from the circuit structure: own tables
(migration 0010), own folder src/estimate-balance and an import-free
shared calculation used by API and UI. Writes go through project commands
(estimate-balance.insert/.update/.delete with complete documents), so
revision checks and Undo/Redo apply; it is not part of project snapshots
or transfer yet. A comparison endpoint sums the device rows of all circuit
lists by cost group (longest prefix) against the estimate.

The UI adds a sidebar entry, a list of Stände (template KG 400, empty or
copy) and a spreadsheet-like editor with autosave, AMEV picker for the
GLF, totals, reserve, maximum current, comparison table and print layout.
The tests reproduce the template example exactly (143.24 kW, 148.48 kVA,
157.56 kW / 163.33 kVA with 10 % reserve, 235.75 A). See
docs/estimate-balance.md and issue #7.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-26 17:39:28 +02:00
Grovy311
cd89c4a499 Add buildings above floors and a building structure page
Projects with several buildings could not be structured: floors and rooms
hung directly off the project. Floors can now belong to a building
(migration 0009: table buildings, nullable floors.building_id). Rooms and
distribution boards keep their floor; their building follows from it.
Existing floors stay without a building.

Buildings use the location-structure command store with
project-building.insert/.update/.delete, inverses and persistent Undo/Redo;
deleting a building with assigned floors is rejected. Floor commands carry
buildingId since command version 2. Version 1 floor commands from existing
history predate buildings and are upgraded with buildingId = null before
they are executed and persisted, so forward and inverse keep one version.

Project snapshot schema 7 stores buildings and floor.buildingId; versions
1-6 are upgraded without buildings. Restore and portable transfer include
buildings, and the transfer remaps building ids.

Buildings, floors and rooms move from the project overview to their own
page /projects/:id/struktur with three columns (Gebäude -> Etagen -> Räume)
that filter each other, and a sidebar entry. Floor selects in the board and
room dialogs are grouped by building. Unchanged dialogs close without a
command. Details in docs/building-structure.md; see issue #6.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-26 12:52:34 +02:00
Grovy311
49488f4e1b Add optional cable-sizing module
Per-circuit cross-section recommendation as a separate module attached to
the circuit list. It never writes project data itself: "Übernehmen" applies
cable type, cross-section and length through the regular circuit.update
command, so revisions and Undo/Redo stay intact.

- Pure domain module (src/cable-sizing) with IEC 60364-5-52:2009 Annex B
  tables for PVC and XLPE, copper and aluminium, methods A1, A2, B1, B2, C,
  D1, D2 and E. Every value was cross-checked against public reproductions;
  where sources differ the lower value is used (docs/cable-sizing-module.md).
- Temperature and grouping between table values round to the safer value;
  values outside the tables return no result instead of a factor of 1.
  Ground methods use B.52.18 (D2) and B.52.19 A (D1).
- Overload protection: circuit-breakers In <= Iz; gG fuses additionally
  I2 <= 1.45 Iz with I2 = 1.6/1.9/2.1 In.
- Inputs prefilled from the circuit: power, phase (group or device rows),
  project voltage, power-weighted cos phi, length and protective device.
- Opened from a "Leitungsberechnung" button in the row actions, not from a
  grid cell, so cable cells keep the spreadsheet behavior.
- Stateless API under /api/cable-sizing; no database table or migration.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-26 11:16:18 +02:00
Grovy311
7692699ee2 Add print cover fields and office profile
- Project settings gain siteAddress, workStage, projectLead and
  projectEditor (project.update-settings schema version 3, migration 0009);
  versions 2 and 1 stay executable and keep the current cover values.
  Snapshot schema 6 carries the fields; older versions upgrade with null.
- Global office profile (office name/address) next to the document logo:
  table document_branding_settings, PUT /api/document-branding/office,
  editable from the print view toolbar.
- Cover page reads all fields; empty values show the "[ergänzen]" marker.
  The Planstände editor column shows the project editor.
- Shared logo constants moved to a dependency-free module so the Next.js
  bundler can import them.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-26 10:39:18 +02:00
Grovy311
4779e4a1a7 Add print view, board info card and document logo upload
- Seitenansicht (/projects/:projectId/print): tabular cover page, board
  overview with supply structure and power sums, one plan per board with a
  repeating title block; PDF via the browser print dialog with named @page
  rules (A4 portrait cover, A4/A3 landscape plans, page x of y).
- Distribution-board info card (board number, location, fed-from, remark)
  in the board edit dialog, persisted through the additively extended
  distribution-board.update command (migration 0008, snapshot schema 6,
  legacy subtree commands normalized).
- Global document logo upload (PNG/JPEG/SVG, max 2 MB) outside project
  revisions and snapshots.
- fed-from stays free text; the overview hierarchy and cumulated sums are
  preliminary until the feed link is modeled.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-26 10:38:59 +02:00
a99980c47b Update docs for the code-review fixes
- circuit-list-editor-api.md: next-identifier moved under
  /projects/:projectId and now documents its 404 scoping behavior.
- current-architecture.md: clarify that the BMK trigger register's
  DB-level normalization is ASCII-only and describe the added
  application-level Unicode-aware uniqueness check that closes the
  umlaut gap; note the additive migration 0006 indexes.

Co-Authored-By: Claude Sonnet 5 <noreply@anthropic.com>
2026-08-06 21:33:28 +02:00
74bea1a3c9 Add Revit circuit list object feed 2026-08-02 18:59:01 +02:00
ab2449419b Add Revit initial import wizard 2026-08-02 17:52:21 +02:00
caa6caf99f Add Revit CSV preview API 2026-08-02 16:49:42 +02:00
44b6fde940 Add public building project setting 2026-07-31 17:41:30 +02:00
43a3bb0b69 Align documentation with clean baseline 2026-07-31 16:41:37 +02:00
1eed19ef6b Add editable project floors and rooms 2026-07-31 14:46:06 +02:00
734a2bcfc4 Create clean release database baseline 2026-07-31 14:07:26 +02:00
5bee3cb103 Add distribution board copy and delete controls 2026-07-31 12:03:52 +02:00
7c8d4a7ddf Document protected circuit groups 2026-07-31 08:06:10 +02:00
7a9530a914 Expose protected tree structure 2026-07-30 20:14:45 +02:00
9d4d4082fe Create protected board defaults 2026-07-30 19:30:53 +02:00
084103bf54 Derive device voltages from project settings 2026-07-29 09:53:58 +02:00
b1a11397b3 Add configurable distribution supply types 2026-07-29 09:31:20 +02:00
ac465a1cc0 Persist project locations 2026-07-26 10:56:29 +02:00
1cf26a932e Persist distribution board setup 2026-07-25 23:41:27 +02:00
1a77eedaa8 Add automatic project snapshots 2026-07-25 23:27:51 +02:00
b2763f72d5 Persist project settings updates 2026-07-25 23:08:07 +02:00
384a5769ab Restore named project snapshots 2026-07-25 22:41:24 +02:00
7c670fece3 Add named project snapshots 2026-07-25 22:15:22 +02:00
5a0c9019af Expose project revision timeline 2026-07-25 21:57:03 +02:00
c45afd0981 Persist section renumbering 2026-07-25 21:30:29 +02:00
abcb468807 Persist circuit reorders 2026-07-25 21:22:10 +02:00
08a2775a88 Persist device row moves 2026-07-25 21:09:02 +02:00
2eba4ea75e Persist circuit structure edits 2026-07-25 20:49:34 +02:00
76d8d59391 Persist circuit cell edits 2026-07-25 20:26:45 +02:00
3977a6e6e1 Persist project device synchronization 2026-07-24 11:47:03 +02:00
e930cb75b8 Route project devices through history 2026-07-24 10:57:50 +02:00
ac16cca77a Add project device structure history 2026-07-24 09:09:59 +02:00
0bc6c7372f Add project device update history 2026-07-24 08:57:57 +02:00
2668fc2f16 Add project device sync history 2026-07-24 08:47:25 +02:00
4b4603b71b Add section renumber history 2026-07-24 08:34:31 +02:00
332dfdb5d9 Add circuit reorder history 2026-07-24 08:21:32 +02:00
53282e8c7c Add placeholder move history 2026-07-23 22:39:59 +02:00
0a51703315 Add device row move history 2026-07-23 22:29:44 +02:00
ca13efbfcb Add circuit history commands 2026-07-23 22:18:36 +02:00
bd5f4f925f Add device row history commands 2026-07-23 22:09:53 +02:00
e4c7cf06e9 Add project command API 2026-07-23 21:56:13 +02:00
1e4dd26bb8 Add persistent history stacks 2026-07-23 21:48:24 +02:00