Also document that Sec-Fetch-Site is only sent over HTTPS, so plain-HTTP
LAN access relies on SameSite=Lax alone.
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Security: per-username login throttling, constant-time unknown-user check,
Sec-Fetch-Site CSRF guard for writes, session rotation on login and
password change, absolute session lifetime, sessions ended on reset and
deactivation, last-admin protection, input length caps, ASCII usernames,
clickjacking headers. Covered by tests/authentication.test.ts.
Filter panel: toggle, fields and count share one row to save space.
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
No self-signup: admins create every account in Config -> Benutzer with a
typed start password; a forced password change gates first use. Session-
cookie auth protects all /api/* routes; /api/users additionally requires
the admin role. See docs/authentication.md.
Co-Authored-By: Claude Sonnet 5 <noreply@anthropic.com>
In LPH 2/3 there are no circuits yet, but the office needs a power
balance by DIN 276 cost group, as in the Excel template "Leistungsbilanz -
KG400": each trade enters consumers by piece or by area (W/m²) with GLF
and cos phi; the balance sums AV and SV per cost group, adds a reserve and
derives the maximum current.
The module is separate from the circuit structure: own tables
(migration 0010), own folder src/estimate-balance and an import-free
shared calculation used by API and UI. Writes go through project commands
(estimate-balance.insert/.update/.delete with complete documents), so
revision checks and Undo/Redo apply; it is not part of project snapshots
or transfer yet. A comparison endpoint sums the device rows of all circuit
lists by cost group (longest prefix) against the estimate.
The UI adds a sidebar entry, a list of Stände (template KG 400, empty or
copy) and a spreadsheet-like editor with autosave, AMEV picker for the
GLF, totals, reserve, maximum current, comparison table and print layout.
The tests reproduce the template example exactly (143.24 kW, 148.48 kVA,
157.56 kW / 163.33 kVA with 10 % reserve, 235.75 A). See
docs/estimate-balance.md and issue #7.
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Projects with several buildings could not be structured: floors and rooms
hung directly off the project. Floors can now belong to a building
(migration 0009: table buildings, nullable floors.building_id). Rooms and
distribution boards keep their floor; their building follows from it.
Existing floors stay without a building.
Buildings use the location-structure command store with
project-building.insert/.update/.delete, inverses and persistent Undo/Redo;
deleting a building with assigned floors is rejected. Floor commands carry
buildingId since command version 2. Version 1 floor commands from existing
history predate buildings and are upgraded with buildingId = null before
they are executed and persisted, so forward and inverse keep one version.
Project snapshot schema 7 stores buildings and floor.buildingId; versions
1-6 are upgraded without buildings. Restore and portable transfer include
buildings, and the transfer remaps building ids.
Buildings, floors and rooms move from the project overview to their own
page /projects/:id/struktur with three columns (Gebäude -> Etagen -> Räume)
that filter each other, and a sidebar entry. Floor selects in the board and
room dialogs are grouped by building. Unchanged dialogs close without a
command. Details in docs/building-structure.md; see issue #6.
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>