List the building structure, room areas, rough power balance and cable
sizing in the README and documentation map, add an architecture section
for the rough power balance, correct stale snapshot schema references and
record the integrated contributor features in the backlog.
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Further Revit exchange will use the CSV export/import of the Linear
plugin instead of Dynamo, as preferred by the internal Revit/CAD
steering committee. Mark the Revit documentation as deferred and remove
the Dynamo diagnostic scripts, which stay reachable through the tag
archive/dynamo-vorueberlegungen.
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Per-circuit cross-section recommendation as a separate module attached to
the circuit list. It never writes project data itself: "Übernehmen" applies
cable type, cross-section and length through the regular circuit.update
command, so revisions and Undo/Redo stay intact.
- Pure domain module (src/cable-sizing) with IEC 60364-5-52:2009 Annex B
tables for PVC and XLPE, copper and aluminium, methods A1, A2, B1, B2, C,
D1, D2 and E. Every value was cross-checked against public reproductions;
where sources differ the lower value is used (docs/cable-sizing-module.md).
- Temperature and grouping between table values round to the safer value;
values outside the tables return no result instead of a factor of 1.
Ground methods use B.52.18 (D2) and B.52.19 A (D1).
- Overload protection: circuit-breakers In <= Iz; gG fuses additionally
I2 <= 1.45 Iz with I2 = 1.6/1.9/2.1 In.
- Inputs prefilled from the circuit: power, phase (group or device rows),
project voltage, power-weighted cos phi, length and protective device.
- Opened from a "Leitungsberechnung" button in the row actions, not from a
grid cell, so cable cells keep the spreadsheet behavior.
- Stateless API under /api/cable-sizing; no database table or migration.
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>