# Future Sizing and Calculation Requirements These requirements are not part of the first implementation, but the structure should support them. ## Goal The app should later support rule-based protection and cable sizing. Future suggestions or checks may include: - protection device type - rated current - tripping characteristic - cable type - number of cores - cable cross-section - minimum cable cross-section based on current - maximum permissible cable length based on voltage drop - warning messages if cable length, cross-section or protection device do not match Users must remain able to manually override suggestions. ## Initial Design Rule Examples These are common planning defaults, not a replacement for full norm-compliant calculation. ### Lighting Circuits Lighting circuits in section `-1Fx` usually use: - protection rated current: 10 A - cable cross-section: 1.5 mm² Typical cable type: - non-DALI lighting: 3x1.5 mm² - DALI-capable lighting: 5x1.5 mm² The app should later suggest the cable type based on whether the connected luminaires require DALI or additional control cores. ### Standard Single-Phase Circuits Standard single-phase circuits in section `-2Fx` usually use: - protection rated current: 16 A - cable cross-section: 2.5 mm² This applies to many typical socket circuits and standard single-phase loads. ### Special Loads and Long Cable Runs For non-standard loads or long cable runs, voltage drop becomes more important. Examples: - instantaneous water heaters - socket combinations with higher connected load - outdoor circuits with long cable routes - lighting circuits with looped-through luminaires and cable lengths of 80 to 100 m The app should later show warnings or require review if voltage drop becomes critical. ## Future Field: Control Requirement To support cable suggestions for lighting circuits, devices or circuits may later include a control requirement. Example values: - none - DALI - KNX - switched only - dimmable - other For lighting circuits: - no additional control cores: suggest 3x1.5 mm² - DALI required: suggest 5x1.5 mm² This must be configurable and manually overridable. ## Future Voltage Drop Check A future voltage drop check may use: - phase type - voltage - circuit total power - apparent power or current - cable material - cable cross-section - cable length - protection rated current - allowed voltage drop The result should be shown as a warning or status indicator, not as an automatic forced change.