Data Model Concept

This is a conceptual model for Codex. It is not a final database schema, but the implementation must preserve these domain relationships.

Core Concept

A distribution board contains a circuit list.

A circuit list contains sections.

A section contains circuits.

A circuit contains zero, one or multiple device rows.

A device row may be:

  • linked to a project device
  • manually entered without a linked project device

ProjectDevice

A project device is a reusable project-specific consumer or consumer group.

A project device can represent:

  • one physical device
  • a recurring device type
  • a consumer group, for example six workstation sockets

User-facing fields:

  • name
  • displayName
  • phaseType
  • connectionKind
  • costGroup
  • category
  • quantity
  • powerPerUnit
  • simultaneityFactor
  • cosPhi
  • totalPower
  • remark

Notes:

  • name is the technical or product-related name, for example E-Line Pro.
  • displayName is a default display name used when inserting the device into the circuit list.
  • After insertion, the circuit list display name is local and not automatically synchronized.
  • quantity is allowed on project devices because a project device may represent a consumer group.
  • Project devices must not define final cable or protection data.

Circuit

A circuit represents one outgoing circuit / equipment identifier in a distribution board section.

User-facing fields:

  • equipmentIdentifier
  • section
  • displayName optional
  • circuitTotalPower
  • protectionType
  • protectionRatedCurrent
  • protectionCharacteristic
  • cableType
  • cableCrossSection
  • cableLength
  • rcdAssignment optional
  • terminalDesignation optional
  • voltage optional
  • status optional
  • isReserve optional
  • remark optional

Circuit-level fields only:

  • protection type
  • protection rated current
  • protection characteristic
  • cable type
  • cable cross-section
  • cable length
  • RCD assignment
  • terminal designation
  • circuit total power

Reason:

Protection and cable data are dimensioned for the complete circuit. They depend on the combined load, installation context, cable length, voltage drop and planning rules.

CircuitDeviceRow

A circuit device row represents a device assigned to a circuit.

User-facing fields:

  • linkedProjectDeviceId optional
  • name
  • displayName
  • phaseType
  • connectionKind optional
  • costGroup optional
  • category optional
  • level
  • roomNumber
  • roomName
  • quantity
  • powerPerUnit
  • simultaneityFactor
  • cosPhi
  • rowTotalPower
  • remark
  • overriddenFields

A circuit device row can be manual.

A manual row has no linked project device.

A manual row can later be saved as a project device. After saving, the row becomes linked to the newly created project device.

Single-Device vs Multi-Device Display

If a circuit has exactly one device row, it is displayed as one compact circuit row.

If a circuit has multiple device rows, it is displayed as:

  • one circuit summary row
  • indented device rows below it

The circuit summary row shows:

  • equipment identifier
  • optional circuit display name
  • circuit total power
  • circuit-level protection data
  • circuit-level cable data

The device rows show:

  • individual device values
  • quantity
  • power
  • cost group
  • category
  • room data
  • remarks

Load Calculation

Device row load:

rowTotalPower = quantity × powerPerUnit × simultaneityFactor

Circuit total:

circuitTotalPower = sum(rowTotalPower of all device rows assigned to the circuit)

cosPhi is stored even if it is not visible in the default table view.

Later apparent power calculation:

apparentPower = totalActivePower / cosPhi

For circuits with multiple devices, apparent power should be calculated per device row and then summed. This avoids losing information when different devices have different power factors.