leistungsbilanz-ts/docs
Grovy311 49488f4e1b Add optional cable-sizing module
Per-circuit cross-section recommendation as a separate module attached to
the circuit list. It never writes project data itself: "Übernehmen" applies
cable type, cross-section and length through the regular circuit.update
command, so revisions and Undo/Redo stay intact.

- Pure domain module (src/cable-sizing) with IEC 60364-5-52:2009 Annex B
  tables for PVC and XLPE, copper and aluminium, methods A1, A2, B1, B2, C,
  D1, D2 and E. Every value was cross-checked against public reproductions;
  where sources differ the lower value is used (docs/cable-sizing-module.md).
- Temperature and grouping between table values round to the safer value;
  values outside the tables return no result instead of a factor of 1.
  Ground methods use B.52.18 (D2) and B.52.19 A (D1).
- Overload protection: circuit-breakers In <= Iz; gG fuses additionally
  I2 <= 1.45 Iz with I2 = 1.6/1.9/2.1 In.
- Inputs prefilled from the circuit: power, phase (group or device rows),
  project voltage, power-weighted cos phi, length and protective device.
- Opened from a "Leitungsberechnung" button in the row actions, not from a
  grid cell, so cable cells keep the spreadsheet behavior.
- Stateless API under /api/cable-sizing; no database table or migration.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-26 11:16:18 +02:00
..
archive Rewrite project documentation 2026-07-23 21:05:43 +02:00
spec Add optional cable-sizing module 2026-09-26 11:16:18 +02:00
cable-sizing-module.md Add optional cable-sizing module 2026-09-26 11:16:18 +02:00
circuit-list-editor-api.md Add optional cable-sizing module 2026-09-26 11:16:18 +02:00
circuit-list-editor-architecture.md Remove circuit structure preview 2026-07-31 14:52:37 +02:00
circuit-list-editor-interactions.md Restore circuit drag placement 2026-07-31 08:33:41 +02:00
circuit-list-editor-known-limitations.md Add optional cable-sizing module 2026-09-26 11:16:18 +02:00
current-architecture.md Add optional cable-sizing module 2026-09-26 11:16:18 +02:00
deployment.md Harden the container runtime and shut down cleanly 2026-09-16 11:04:34 +02:00
development-workflow.md Create clean release database baseline 2026-07-31 14:07:26 +02:00
project-history-and-external-model-architecture.md Add public building project setting 2026-07-31 17:41:30 +02:00
README.md Add optional cable-sizing module 2026-09-26 11:16:18 +02:00
revit-requirements-llm-context.md Add public building project setting 2026-07-31 17:41:30 +02:00

Dokumentationsübersicht

Diese Seite ist der Einstieg in die Projektdokumentation. Aussagen zum aktuellen System stehen unter „Aktuell“. Zukunftsentwürfe und historische Unterlagen sind ausdrücklich getrennt und dürfen nicht als bereits implementiert verstanden werden.

Aktuell

Entwicklung und Betrieb

Zukunftsarchitektur

Fachliche Referenzspezifikation

Die folgenden Dokumente beschreiben Zielregeln und Anforderungen. Nicht jeder Punkt ist bereits umgesetzt; der aktuelle Stand ergibt sich aus Architektur, Limitierungen und Roadmap.

Archiv