leistungsbilanz-ts/src/server/index.ts
Grovy311 49488f4e1b Add optional cable-sizing module
Per-circuit cross-section recommendation as a separate module attached to
the circuit list. It never writes project data itself: "Übernehmen" applies
cable type, cross-section and length through the regular circuit.update
command, so revisions and Undo/Redo stay intact.

- Pure domain module (src/cable-sizing) with IEC 60364-5-52:2009 Annex B
  tables for PVC and XLPE, copper and aluminium, methods A1, A2, B1, B2, C,
  D1, D2 and E. Every value was cross-checked against public reproductions;
  where sources differ the lower value is used (docs/cable-sizing-module.md).
- Temperature and grouping between table values round to the safer value;
  values outside the tables return no result instead of a factor of 1.
  Ground methods use B.52.18 (D2) and B.52.19 A (D1).
- Overload protection: circuit-breakers In <= Iz; gG fuses additionally
  I2 <= 1.45 Iz with I2 = 1.6/1.9/2.1 In.
- Inputs prefilled from the circuit: power, phase (group or device rows),
  project voltage, power-weighted cos phi, length and protective device.
- Opened from a "Leitungsberechnung" button in the row actions, not from a
  grid cell, so cable cells keep the spreadsheet behavior.
- Stateless API under /api/cable-sizing; no database table or migration.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-26 11:16:18 +02:00

114 lines
3.5 KiB
TypeScript

import express from "express";
import { globalDeviceRouter } from "./routes/global-device.routes.js";
import { projectDeviceRouter } from "./routes/project-device.routes.js";
import { projectRouter } from "./routes/project.routes.js";
import { cableSizingRouter } from "./routes/cable-sizing.routes.js";
import { errorMiddleware } from "./middleware/error.middleware.js";
import { createLogger, toErrorMeta } from "../shared/logging/logger.js";
import { closeDefaultDatabase } from "../db/client.js";
const logger = createLogger("api");
const app = express();
const port = Number(process.env.PORT || 3000);
const heartbeatIntervalMs = 5 * 60 * 1000;
const shutdownTimeoutMs = 15 * 1000;
app.use(express.json({ limit: "25mb" }));
app.use((req, res, next) => {
if (req.path === "/health") {
next();
return;
}
const startedAt = Date.now();
logger.debug("request started", { method: req.method, path: req.originalUrl });
res.on("finish", () => {
const meta = {
method: req.method,
path: req.originalUrl,
status: res.statusCode,
durationMs: Date.now() - startedAt,
};
if (res.statusCode >= 500) logger.error("request completed", meta);
else if (res.statusCode >= 400) logger.warn("request completed", meta);
else logger.info("request completed", meta);
});
res.on("close", () => {
if (!res.writableEnded) {
logger.warn("request aborted before response finished", {
method: req.method,
path: req.originalUrl,
durationMs: Date.now() - startedAt,
});
}
});
next();
});
app.get("/health", (_req, res) => {
res.json({ ok: true });
});
app.use("/api/cable-sizing", cableSizingRouter);
app.use("/api/projects", projectRouter);
app.use("/api/global-devices", globalDeviceRouter);
app.use("/api/project-devices", projectDeviceRouter);
app.use(errorMiddleware);
process.on("uncaughtException", (error) => {
logger.error("uncaught exception, exiting", toErrorMeta(error));
process.exit(1);
});
process.on("unhandledRejection", (reason) => {
logger.error("unhandled rejection, exiting", toErrorMeta(reason));
process.exit(1);
});
setInterval(() => {
const memory = process.memoryUsage();
logger.verbose("heartbeat", {
uptimeSeconds: Math.round(process.uptime()),
rssMb: Math.round(memory.rss / 1024 / 1024),
heapUsedMb: Math.round(memory.heapUsed / 1024 / 1024),
});
}, heartbeatIntervalMs).unref();
const server = app.listen(port, () => {
logger.info("server started", { port });
});
let shuttingDown = false;
function shutdown(signal: NodeJS.Signals): void {
if (shuttingDown) return;
shuttingDown = true;
logger.info("shutting down", { signal });
// Falls ein Request haengt oder ein Socket nicht freigegeben wird, soll der
// Prozess trotzdem enden, statt auf das SIGKILL des Containers zu warten.
const forceExit = setTimeout(() => {
logger.error("shutdown timed out, forcing exit");
process.exit(1);
}, shutdownTimeoutMs);
forceExit.unref();
server.close((error) => {
if (error) logger.error("http server close failed", toErrorMeta(error));
try {
closeDefaultDatabase();
} catch (closeError) {
logger.error("database close failed", toErrorMeta(closeError));
}
logger.info("shutdown complete");
process.exit(error ? 1 : 0);
});
// Ohne das warten offene Keep-Alive-Verbindungen (z. B. die des
// Next.js-Servers) den Timeout oben aus; laufende Requests laufen weiter.
server.closeIdleConnections();
}
process.on("SIGTERM", shutdown);
process.on("SIGINT", shutdown);