leistungsbilanz-ts/docs/spec/08-current-product-backlog.md
Grovy311 49488f4e1b Add optional cable-sizing module
Per-circuit cross-section recommendation as a separate module attached to
the circuit list. It never writes project data itself: "Übernehmen" applies
cable type, cross-section and length through the regular circuit.update
command, so revisions and Undo/Redo stay intact.

- Pure domain module (src/cable-sizing) with IEC 60364-5-52:2009 Annex B
  tables for PVC and XLPE, copper and aluminium, methods A1, A2, B1, B2, C,
  D1, D2 and E. Every value was cross-checked against public reproductions;
  where sources differ the lower value is used (docs/cable-sizing-module.md).
- Temperature and grouping between table values round to the safer value;
  values outside the tables return no result instead of a factor of 1.
  Ground methods use B.52.18 (D2) and B.52.19 A (D1).
- Overload protection: circuit-breakers In <= Iz; gG fuses additionally
  I2 <= 1.45 Iz with I2 = 1.6/1.9/2.1 In.
- Inputs prefilled from the circuit: power, phase (group or device rows),
  project voltage, power-weighted cos phi, length and protective device.
- Opened from a "Leitungsberechnung" button in the row actions, not from a
  grid cell, so cable cells keep the spreadsheet behavior.
- Stateless API under /api/cable-sizing; no database table or migration.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-26 11:16:18 +02:00

7 KiB

Current Product Backlog

This document records the next agreed product improvements. It describes requirements and intended sequencing, not proof of implementation.

Circuit List Editor

  • Collect the remaining editor interaction issues before changing additional behavior.

Distribution Board Components and Protection Groups

  • Implement the agreed protected circuit-group and distribution-board component model in phased work packages.
  • Phase A: central protection catalog, validation, defaults and pure grouped BMK rules.
  • Phase B1: relational group, component and protection tables with shared BMK uniqueness.
  • Phase B2: complete snapshot/transfer schema for the supported project state.
  • Phase C1: new-board command with three groups and fixed header components.
  • Phase C2a1: persistent insert/delete commands for mutable group protection and auxiliary components.
  • Phase C2a2: component update and reorder commands.
  • Phase C2b1: empty-group insert/update/delete commands.
  • Phase C2b2: complete group reorder command.
  • Phase D1a: deterministic collision-aware group-renumber plan.
  • Phase D1b: persistent collision-safe group-renumber command.
  • Phase D2a: deterministic same-category circuit-move plan.
  • Phase D2b: persistent same-category circuit-move command.
  • Phase D3a: complete validated group-subtree snapshot and warning summary.
  • Phase D3b: persistent populated-group delete/restore command.
  • Phase E1: tree read model for components, groups and protection devices.
  • Phase E2a: pure header/group/footer structure projection.
  • Phase E2b: render the structure projection in the editor grid.
  • Phase E3a: create, edit and delete mutable group and footer components.
  • Phase E3b1: create, rename and safely delete empty circuit groups.
  • Phase E3b2a: persistent circuit-protection update command.
  • Phase E3b2b: circuit-protection defaults on insert and editor modal.
  • Phase E4a: persistent same-category group reorder controls.
  • Phase E4b: explicit group renumber, circuit moves and populated-delete warning.
    • Explicit same-category group renumbering updates prefixes and all child BMK atomically.
    • Single-circuit moves between same-category groups with automatic next-free BMK assignment.
    • Populated-group delete warning and explicit subtree deletion.
  • Phase E: editor projection and editing.
  • Phase F: documentation and full GUI verification.
  • Keep full electrical sizing and cable-dimensioning rules separate until the planner supplies the calculation requirements. The optional per-circuit cable sizing module (docs/cable-sizing-module.md) exists; its tables must be confirmed by the planner against DIN VDE 0298-4.
  • Detailed specification: docs/spec/09-distribution-board-components-and-protection-groups.md

First Release Baseline

The pre-release cleanup established the following compatibility boundary:

  • Pre-baseline databases, portable JSON exports, logical snapshots and persisted command histories are explicitly unsupported.
  • Migration 0000 builds the complete supported schema on an empty database.
  • The development migration chain and Drizzle metadata were replaced before any supported release depended on them.
  • Upgrade-only database, snapshot and command compatibility paths were removed.
  • Pre-cleanup development history remains available through Git history.
  • Clean installation, migration, startup and core workflows were verified against an empty database.
  • Mark this compatibility boundary with the first supported release tag.
  • After that release, every published migration is immutable and later schema changes must use new additive migrations.

Project History

  • Every listed logical snapshot, including automatic snapshots, must be explicitly restorable from the project history UI.
  • Show which project change produced a snapshot. Prefer immutable revision metadata over storing a second free-form description of the same change.
  • Keep restoration auditable as a new project revision and preserve persistent undo/redo.

Distribution Boards

  • Assign an optional project floor to a distribution board.
  • Store a supply classification for each distribution board:
    • AV (Allgemeine Stromversorgung)
    • SV (Sicherheitsstromversorgung)
    • EV (Ersatzstromversorgung)
    • USV (Unterbrechungsfreie Stromversorgung)
    • MSR (Mess-, Steuerungs- und Regelungstechnik)
    • SiBe (Sicherheitsbeleuchtung)
  • Let project settings select which catalog supply types are used in a project. Distribution-board dialogs offer only that selection; a type in use cannot be disabled.
  • Include both fields in project snapshots and portable project export/import.
  • Persist changes through project commands so they remain undoable after a restart.

Device Voltage Derivation

  • Derive voltage from the selected phase type and the project settings:
    • single-phase uses the project's single-phase voltage;
    • three-phase uses the project's three-phase voltage.
  • Voltage is not editable on global devices, project devices or circuits. Global devices store only their phase; copying one into a project derives the target project's voltage.
  • Project-device voltage follows its phase. Circuit voltage follows the section phase; an unassigned circuit is three-phase only when all assigned device rows with a valid phase are three-phase.
  • Changing project voltage settings updates all project devices and circuits atomically in the same persistent Undo/Redo step.
  • Baseline migration 0000 stores only canonical derived values. Pre-baseline imports are intentionally unsupported.

Building Classification

  • Store whether a project represents a public building.
  • Edit the value in the project settings and preserve it through persistent Undo/Redo, snapshots and portable project transfers.
  • Provide the value as an explicit future sizing input for selecting halogen-free cables and lines; automatic sizing remains deferred.

Circuit List Power Summary

  • Show the total power of every circuit section.
  • Show the unadjusted total power of the complete distribution board.
  • Store a distribution-board simultaneity factor between zero and one in the distribution-board settings.
  • Show the distribution-board total after applying that factor.
  • Preserve the factor in project commands, snapshots and portable project transfers.
  • Keep column visibility and order as a project-specific UI preference so all distribution boards in the same project open with the same columns.
  1. Distribution-board floor and supply fields.
  2. Device voltage derivation without overrides.
  3. Snapshot-to-revision descriptions and history presentation.
  4. Distribution-board power summary and project column layout.

The Revit/CSV/IFCGUID round-trip follows the distribution-board component foundation as a separate jointly planned phase and must not be inferred from these tasks.