Commit graph

45 commits

Author SHA1 Message Date
4ff01b2ccd Harden Linear XLSX end to end 2026-09-30 21:02:20 +02:00
d4803a18d2 Document Linear Excel integration 2026-09-29 22:28:16 +02:00
b74b495fab Update print view and documentation for logical feeds 2026-09-28 20:57:58 +02:00
b50c00c0ac Bring documentation in line with integrated features
List the building structure, room areas, rough power balance and cable
sizing in the README and documentation map, add an architecture section
for the rough power balance, correct stale snapshot schema references and
record the integrated contributor features in the backlog.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-27 20:36:43 +02:00
5cbbd3a84a Align cable sizing with DIN VDE 0298-4 2026-09-27 17:01:23 +02:00
598003554a Merge remote-tracking branch 'origin/main' into feature/cable-sizing 2026-09-27 16:54:12 +02:00
b9462e61c5 Defer Revit work and remove Dynamo scripts
Further Revit exchange will use the CSV export/import of the Linear
plugin instead of Dynamo, as preferred by the internal Revit/CAD
steering committee. Mark the Revit documentation as deferred and remove
the Dynamo diagnostic scripts, which stay reachable through the tag
archive/dynamo-vorueberlegungen.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-27 10:51:13 +02:00
Grovy311
49488f4e1b Add optional cable-sizing module
Per-circuit cross-section recommendation as a separate module attached to
the circuit list. It never writes project data itself: "Übernehmen" applies
cable type, cross-section and length through the regular circuit.update
command, so revisions and Undo/Redo stay intact.

- Pure domain module (src/cable-sizing) with IEC 60364-5-52:2009 Annex B
  tables for PVC and XLPE, copper and aluminium, methods A1, A2, B1, B2, C,
  D1, D2 and E. Every value was cross-checked against public reproductions;
  where sources differ the lower value is used (docs/cable-sizing-module.md).
- Temperature and grouping between table values round to the safer value;
  values outside the tables return no result instead of a factor of 1.
  Ground methods use B.52.18 (D2) and B.52.19 A (D1).
- Overload protection: circuit-breakers In <= Iz; gG fuses additionally
  I2 <= 1.45 Iz with I2 = 1.6/1.9/2.1 In.
- Inputs prefilled from the circuit: power, phase (group or device rows),
  project voltage, power-weighted cos phi, length and protective device.
- Opened from a "Leitungsberechnung" button in the row actions, not from a
  grid cell, so cable cells keep the spreadsheet behavior.
- Stateless API under /api/cable-sizing; no database table or migration.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-26 11:16:18 +02:00
44b6fde940 Add public building project setting 2026-07-31 17:41:30 +02:00
43a3bb0b69 Align documentation with clean baseline 2026-07-31 16:41:37 +02:00
4a859f31b8 Complete protected circuit group phase 2026-07-31 08:59:12 +02:00
7c8d4a7ddf Document protected circuit groups 2026-07-31 08:06:10 +02:00
ab989cc637 Delete populated circuit groups safely 2026-07-31 08:01:55 +02:00
93ec294759 Move circuits between groups 2026-07-31 07:58:42 +02:00
be9c6f0d52 Renumber circuit groups explicitly 2026-07-31 07:53:07 +02:00
0cb280ddb2 Reorder circuit groups 2026-07-31 07:47:45 +02:00
8898117ed4 Configure circuit protection 2026-07-31 07:45:48 +02:00
18ca5eb3d4 Persist circuit protection updates 2026-07-31 07:37:38 +02:00
0c92fbd09e Manage circuit groups 2026-07-31 07:32:46 +02:00
756e307bd8 Manage distribution board components 2026-07-31 07:29:25 +02:00
31589875b5 Render protected circuit structure 2026-07-31 07:22:26 +02:00
ac21d6eb5d WIP multiple sections 2026-07-30 20:27:17 +02:00
7a9530a914 Expose protected tree structure 2026-07-30 20:14:45 +02:00
99bdf6491b Persist populated group deletion 2026-07-30 20:10:10 +02:00
db4c757018 Define circuit group subtrees 2026-07-30 20:06:09 +02:00
3399fcd88b Persist circuit group moves 2026-07-30 20:03:11 +02:00
9ad91887b2 Plan circuit group moves 2026-07-30 19:58:45 +02:00
07925b2fd9 Persist circuit group renumbering 2026-07-30 19:56:59 +02:00
63650a623c Plan circuit group renumbering 2026-07-30 19:51:44 +02:00
e702712bd8 Add circuit group reordering 2026-07-30 19:49:27 +02:00
1250f9a6af Add circuit group commands 2026-07-30 19:46:55 +02:00
69b020339e Add component update commands 2026-07-30 19:42:09 +02:00
604604f056 Add component structure commands 2026-07-30 19:38:48 +02:00
9d4d4082fe Create protected board defaults 2026-07-30 19:30:53 +02:00
012308984d Include components in project snapshots 2026-07-30 19:24:28 +02:00
e7607c90c4 Add component persistence foundation 2026-07-30 19:15:00 +02:00
a88c4b2086 Add protection domain foundation 2026-07-30 19:03:36 +02:00
a72d2c76e0 Specify protected circuit groups 2026-07-30 18:52:26 +02:00
fac6c9350f Document first release baseline 2026-07-29 19:23:07 +02:00
9ea081179d Add distribution power summaries 2026-07-29 19:02:18 +02:00
dcb303284c Describe snapshot source revisions 2026-07-29 11:52:26 +02:00
084103bf54 Derive device voltages from project settings 2026-07-29 09:53:58 +02:00
b1a11397b3 Add configurable distribution supply types 2026-07-29 09:31:20 +02:00
194bc9c0b1 Add project overview import 2026-07-29 08:36:57 +02:00
a04c2c04d4 Document current product backlog 2026-07-28 22:28:05 +02:00