Commit graph

38 commits

Author SHA1 Message Date
Grovy311
49488f4e1b Add optional cable-sizing module
Per-circuit cross-section recommendation as a separate module attached to
the circuit list. It never writes project data itself: "Übernehmen" applies
cable type, cross-section and length through the regular circuit.update
command, so revisions and Undo/Redo stay intact.

- Pure domain module (src/cable-sizing) with IEC 60364-5-52:2009 Annex B
  tables for PVC and XLPE, copper and aluminium, methods A1, A2, B1, B2, C,
  D1, D2 and E. Every value was cross-checked against public reproductions;
  where sources differ the lower value is used (docs/cable-sizing-module.md).
- Temperature and grouping between table values round to the safer value;
  values outside the tables return no result instead of a factor of 1.
  Ground methods use B.52.18 (D2) and B.52.19 A (D1).
- Overload protection: circuit-breakers In <= Iz; gG fuses additionally
  I2 <= 1.45 Iz with I2 = 1.6/1.9/2.1 In.
- Inputs prefilled from the circuit: power, phase (group or device rows),
  project voltage, power-weighted cos phi, length and protective device.
- Opened from a "Leitungsberechnung" button in the row actions, not from a
  grid cell, so cable cells keep the spreadsheet behavior.
- Stateless API under /api/cable-sizing; no database table or migration.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-09-26 11:16:18 +02:00
44b6fde940 Add public building project setting 2026-07-31 17:41:30 +02:00
43a3bb0b69 Align documentation with clean baseline 2026-07-31 16:41:37 +02:00
4a859f31b8 Complete protected circuit group phase 2026-07-31 08:59:12 +02:00
7c8d4a7ddf Document protected circuit groups 2026-07-31 08:06:10 +02:00
ab989cc637 Delete populated circuit groups safely 2026-07-31 08:01:55 +02:00
93ec294759 Move circuits between groups 2026-07-31 07:58:42 +02:00
be9c6f0d52 Renumber circuit groups explicitly 2026-07-31 07:53:07 +02:00
0cb280ddb2 Reorder circuit groups 2026-07-31 07:47:45 +02:00
8898117ed4 Configure circuit protection 2026-07-31 07:45:48 +02:00
18ca5eb3d4 Persist circuit protection updates 2026-07-31 07:37:38 +02:00
0c92fbd09e Manage circuit groups 2026-07-31 07:32:46 +02:00
756e307bd8 Manage distribution board components 2026-07-31 07:29:25 +02:00
31589875b5 Render protected circuit structure 2026-07-31 07:22:26 +02:00
ac21d6eb5d WIP multiple sections 2026-07-30 20:27:17 +02:00
7a9530a914 Expose protected tree structure 2026-07-30 20:14:45 +02:00
99bdf6491b Persist populated group deletion 2026-07-30 20:10:10 +02:00
db4c757018 Define circuit group subtrees 2026-07-30 20:06:09 +02:00
3399fcd88b Persist circuit group moves 2026-07-30 20:03:11 +02:00
9ad91887b2 Plan circuit group moves 2026-07-30 19:58:45 +02:00
07925b2fd9 Persist circuit group renumbering 2026-07-30 19:56:59 +02:00
63650a623c Plan circuit group renumbering 2026-07-30 19:51:44 +02:00
e702712bd8 Add circuit group reordering 2026-07-30 19:49:27 +02:00
1250f9a6af Add circuit group commands 2026-07-30 19:46:55 +02:00
69b020339e Add component update commands 2026-07-30 19:42:09 +02:00
604604f056 Add component structure commands 2026-07-30 19:38:48 +02:00
9d4d4082fe Create protected board defaults 2026-07-30 19:30:53 +02:00
012308984d Include components in project snapshots 2026-07-30 19:24:28 +02:00
e7607c90c4 Add component persistence foundation 2026-07-30 19:15:00 +02:00
a88c4b2086 Add protection domain foundation 2026-07-30 19:03:36 +02:00
a72d2c76e0 Specify protected circuit groups 2026-07-30 18:52:26 +02:00
fac6c9350f Document first release baseline 2026-07-29 19:23:07 +02:00
9ea081179d Add distribution power summaries 2026-07-29 19:02:18 +02:00
dcb303284c Describe snapshot source revisions 2026-07-29 11:52:26 +02:00
084103bf54 Derive device voltages from project settings 2026-07-29 09:53:58 +02:00
b1a11397b3 Add configurable distribution supply types 2026-07-29 09:31:20 +02:00
194bc9c0b1 Add project overview import 2026-07-29 08:36:57 +02:00
a04c2c04d4 Document current product backlog 2026-07-28 22:28:05 +02:00