45 lines
3 KiB
Markdown
45 lines
3 KiB
Markdown
# Circuit List Editor Known Limitations
|
|
|
|
- All currently supported Circuit and CircuitDeviceRow editor writes use
|
|
persistent project commands and project-wide toolbar undo/redo, including
|
|
moves, atomic multi-section reorders and explicit renumbering. Undo/redo
|
|
eligibility is restored from server history after a page reload.
|
|
- The project page exposes the paginated revision timeline; the circuit editor
|
|
itself currently exposes only the next eligible Undo/Redo actions.
|
|
- Named and automatic logical project snapshots can be listed and restored
|
|
through the project page with persistent Undo/Redo. Automatic snapshots are
|
|
created every 25 revisions and only their newest 12 entries are retained.
|
|
- Die Linear-XLSX-Anbindung bis R9 ist umgesetzt: Erst- und Folgeimport,
|
|
Objektplanung und Editorzuordnung, strukturtreue Rückgabe sowie bestätigtes
|
|
Löschen fehlender Objekte verwenden persistente Commands. Offen ist die
|
|
R10-Härtung des gesamten Ablaufs mit mehreren Tausend synthetischen Objekten,
|
|
Messungen sowie Snapshot-/Transfer- und Neustarttests.
|
|
- Persistence currently targets local SQLite; PostgreSQL is an architectural option, not an implemented runtime.
|
|
- The global device library supports basic CRUD and copy operations, but has no
|
|
versioning, permissions or controlled synchronization model.
|
|
- There is no automatic sizing of all circuits. The optional cable sizing
|
|
module suggests a cross-section for one circuit on demand using
|
|
DIN VDE 0298-4:2023-06 with Berichtigung 1:2023-10. It excludes direct
|
|
burial, grouped method E and neutral-current sizing above 33 % third
|
|
harmonic, and it does not check short-circuit withstand, disconnection time
|
|
or selectivity. See `docs/cable-sizing-module.md`.
|
|
- Sorting is view-only until users explicitly apply sorted order.
|
|
- Complete-circuit drag supports one circuit at a time between groups of the
|
|
same category. Cross-category moves and multi-circuit moves across group
|
|
boundaries are intentionally rejected; multi-circuit reorder inside one
|
|
group remains supported.
|
|
- Protection and cable values are planner-owned manual selections. The later
|
|
sizing/warning engine does not yet validate them against load, length or
|
|
voltage-drop rules.
|
|
- One logical incoming feed per distribution board is supported. A second or
|
|
replacement feed with changeover semantics (for example SV/SiBe) is still a
|
|
follow-up. `fedFrom` remains the free-text field for external sources and
|
|
supplementary notes. Revit does not yet propose logical feed links.
|
|
- A logical link without a selected feeding circuit appears in the hierarchy,
|
|
but deliberately contributes no load to an upstream circuit until the planner
|
|
selects that circuit (see `docs/print-view.md`).
|
|
- The print view uses a kbp corporate design derived from logo and
|
|
presentation material. Snapshots do not record an editor, so the cover's
|
|
Planstände list shows the project's current editor for every entry. On screen, long
|
|
board plans are not split into pages; pagination happens in the browser print
|
|
dialog.
|