# Data Model Concept
This is a conceptual model for Codex. It is not a final database schema, but the implementation must preserve these domain relationships.
## Core Concept
A distribution board contains a circuit list.
A circuit list contains sections.
A section contains circuits.
A circuit contains zero, one or multiple device rows.
A device row may be:
- linked to a project device
- manually entered without a linked project device
## ProjectDevice
A project device is a reusable project-specific consumer or consumer group.
A project device can represent:
- one physical device
- a recurring device type
- a consumer group, for example six workstation sockets
User-facing fields:
- `name`
- `displayName`
- `phaseType`
- `connectionKind`
- `costGroup`
- `category`
- `quantity`
- `powerPerUnit`
- `simultaneityFactor`
- `cosPhi`
- `totalPower`
- `remark`
Notes:
- `name` is the technical or product-related name, for example `E-Line Pro`.
- `displayName` is a default display name used when inserting the device into the circuit list.
- After insertion, the circuit list display name is local and not automatically synchronized.
- `quantity` is allowed on project devices because a project device may represent a consumer group.
- Project devices must not define final cable or protection data.
## Circuit
A circuit represents one outgoing circuit / equipment identifier in a distribution board section.
User-facing fields:
- `equipmentIdentifier`
- `section`
- `displayName` optional
- `circuitTotalPower`
- `protectionType`
- `protectionRatedCurrent`
- `protectionCharacteristic`
- `cableType`
- `cableCrossSection`
- `cableLength`
- `rcdAssignment` optional
- `terminalDesignation` optional
- `voltage` optional
- `status` optional
- `isReserve` optional
- `remark` optional
Circuit-level fields only:
- protection type
- protection rated current
- protection characteristic
- cable type
- cable cross-section
- cable length
- RCD assignment
- terminal designation
- circuit total power
Reason:
Protection and cable data are dimensioned for the complete circuit. They depend on the combined load, installation context, cable length, voltage drop and planning rules.
## CircuitDeviceRow
A circuit device row represents a device assigned to a circuit.
User-facing fields:
- `linkedProjectDeviceId` optional
- `name`
- `displayName`
- `phaseType`
- `connectionKind` optional
- `costGroup` optional
- `category` optional
- `level`
- `roomNumber`
- `roomName`
- `quantity`
- `powerPerUnit`
- `simultaneityFactor`
- `cosPhi`
- `rowTotalPower`
- `remark`
- `overriddenFields`
A circuit device row can be manual.
A manual row has no linked project device.
A manual row can later be saved as a project device. After saving, the row becomes linked to the newly created project device.
## Single-Device vs Multi-Device Display
If a circuit has exactly one device row, it is displayed as one compact circuit row.
If a circuit has multiple device rows, it is displayed as:
- one circuit summary row
- indented device rows below it
The circuit summary row shows:
- equipment identifier
- optional circuit display name
- circuit total power
- circuit-level protection data
- circuit-level cable data
The device rows show:
- individual device values
- quantity
- power
- cost group
- category
- room data
- remarks
## Load Calculation
Device row load:
```text
rowTotalPower = quantity × powerPerUnit × simultaneityFactor
```
Circuit total:
```text
circuitTotalPower = sum(rowTotalPower of all device rows assigned to the circuit)
```
`cosPhi` is stored even if it is not visible in the default table view.
Later apparent power calculation:
```text
apparentPower = totalActivePower / cosPhi
```
For circuits with multiple devices, apparent power should be calculated per device row and then summed. This avoids losing information when different devices have different power factors.