# Future Sizing and Calculation Requirements
|
|
|
|
These requirements are not part of the first implementation, but the structure should support them.
|
|
|
|
## Goal
|
|
|
|
The app should later support rule-based protection and cable sizing.
|
|
|
|
Future suggestions or checks may include:
|
|
|
|
- protection device type
|
|
- rated current
|
|
- tripping characteristic
|
|
- cable type
|
|
- number of cores
|
|
- cable cross-section
|
|
- minimum cable cross-section based on current
|
|
- maximum permissible cable length based on voltage drop
|
|
- warning messages if cable length, cross-section or protection device do not match
|
|
|
|
Users must remain able to manually override suggestions.
|
|
|
|
## Initial Design Rule Examples
|
|
|
|
These are common planning defaults, not a replacement for full norm-compliant calculation.
|
|
|
|
### Lighting Circuits
|
|
|
|
Lighting circuits in section `-1Fx` usually use:
|
|
|
|
- protection rated current: 10 A
|
|
- cable cross-section: 1.5 mm²
|
|
|
|
Typical cable type:
|
|
|
|
- non-DALI lighting: 3x1.5 mm²
|
|
- DALI-capable lighting: 5x1.5 mm²
|
|
|
|
The app should later suggest the cable type based on whether the connected luminaires require DALI or additional control cores.
|
|
|
|
### Standard Single-Phase Circuits
|
|
|
|
Standard single-phase circuits in section `-2Fx` usually use:
|
|
|
|
- protection rated current: 16 A
|
|
- cable cross-section: 2.5 mm²
|
|
|
|
This applies to many typical socket circuits and standard single-phase loads.
|
|
|
|
### Special Loads and Long Cable Runs
|
|
|
|
For non-standard loads or long cable runs, voltage drop becomes more important.
|
|
|
|
Examples:
|
|
|
|
- instantaneous water heaters
|
|
- socket combinations with higher connected load
|
|
- outdoor circuits with long cable routes
|
|
- lighting circuits with looped-through luminaires and cable lengths of 80 to 100 m
|
|
|
|
The app should later show warnings or require review if voltage drop becomes critical.
|
|
|
|
## Future Field: Control Requirement
|
|
|
|
To support cable suggestions for lighting circuits, devices or circuits may later include a control requirement.
|
|
|
|
Example values:
|
|
|
|
- none
|
|
- DALI
|
|
- KNX
|
|
- switched only
|
|
- dimmable
|
|
- other
|
|
|
|
For lighting circuits:
|
|
|
|
- no additional control cores: suggest 3x1.5 mm²
|
|
- DALI required: suggest 5x1.5 mm²
|
|
|
|
This must be configurable and manually overridable.
|
|
|
|
## Future Voltage Drop Check
|
|
|
|
A future voltage drop check may use:
|
|
|
|
- phase type
|
|
- voltage
|
|
- circuit total power
|
|
- apparent power or current
|
|
- cable material
|
|
- cable cross-section
|
|
- cable length
|
|
- protection rated current
|
|
- allowed voltage drop
|
|
|
|
The result should be shown as a warning or status indicator, not as an automatic forced change.
|